DB36/T 1493-2021 基于窄带物联网(NB-IoT)的供水管网漏损监测系统技术指南
ICS17.120
A50 DB36
江西省地方标准
DB36/T1493-2021
基于窄带物联网(B-IoT)的供水管网 漏损监测系统 技术指南
Technical guide for leakage monitoring system of water supply network based on NarrowBand Internet of Things(NB-IoT)
2021-12-14发布2022-06-01实施
江西省市场监督管理局发布
1范围
本文件规定了基于窄带物联网(B-oT)的供水管网漏损监测系统术语和定义、技术要求。本文件适用于住宅小区、校园、工业园区和公共机构等用水单位的基于窄带物联网(NB-oT)的供水管网漏损监测系统。
2规范性引用文件
下列文件中的内容通过文中的规范性引用而构成本文件必不可少的条款其中,注日期的引用文件,仅该日期对成的版本适用于本文件:不注日期的引用文件,其最新版本(包括所有的修改单)适用于本文件。
GBT12452企业水平衡则试通则
GBT19582(所有部分)基于Modbus协议的工业自动化网络规范
GB24789用水单位水计量器具配备和管理通则
GB50093自动化仪表工程施工及质量验收规范
CJT188用户计量仪表数据传输技术条件
3术语和定义
下列术语和定义适用于本文件。
3.1
水平新Water balance
用水单位各用水单元或系统的输入水量之和成等于输出水量之和。
3.2
水平衡测试Water balance test
对用水单元和用水系统的水量进行系统的测试、统计、分析得出水平衡关系的过程。
3.3
分区计量District Metering Area,DMA
通过截断管段或关闭管段上阀门的方法,将管网分为若干个相对独立的区域,并在每个区域的进水管和出水管上安装流量计,从而实现对各个区域入水流量与出水流量的监测。
3.4
背景漏失水量Background leakage
现有技术手段和措施未能检测到的管网漏点的损失水量。
3.5
管网漏损员监测系统Network leakage mon itor ing system
针对供水管网系统安装DM分区计量装置,并通过采用远程传输等方式及时采集各分区计量在线流量仪表数据,是实现供水管网系统管网漏损在线监测和动态分析功能的硬件系统和软件系统的统称。
3.6
窄带物联网Narrow Band Intemet of Things,NB-loT
支持低功耗设备在广域网的蜂窝数据连接,也被叫作低功耗广域网(PWA)。
3.7
NB-loT数据采集器NB-loT Data coll ector
在采用B-ōT无线通信技术的一种信息采集的设备。它通过信道对其管辖的分区计量装置的信息进行采集、处理和存储,并通过远程信道与数据中心交换数据。
3.8
在线水流量仪表0nline water flow meter
用来测量水流量并带实时数据远传功能的自动化仪表,如远传水表、在线水流量计等。
4技术要求
4.1管网漏损监测系统构架
4.1.1系统示意图
系统由感知层、传输层、数据层和应用决策层组成见图1,系统部署在管网管理部门及授权用户终端等。4.1.2基本功能
可通过对各DM区域内的流量和压力节点实施远程实时监测,既可及时发现管网供水异常,又可测算出区域的漏损情况、并辅助查找漏点,有效降低管网漏损率。系统成具备但不限于以下功能:
1)水平衡测试:具有分析计算水平衡功能。
2)漏损量计算:具有各层DMA分区温损量计算的核心算法。
3)大数据集成分析:具有集成不同的数据源进行数据分析和挖掘功能。
4)漏损管理:具有依据计算分析结果指导主动漏损预警和控制功能。
5)监控报警:具有突发爆管重大泄漏事件的实时报整功能。
6)表务分析:具有分析流量仪表口径与管道流量是香匹配,并可进行远程自动抄表功能。
7)用户管理:具有不同用户角色不同权限的统一管理功能。
8)系统管理:具有分区设置、基于管网拓扑结构进行多级分区计量的设置,不同算法的参数设置等功能。
9)信息共享:具有Wb发布功能。
10)安全管理:具有授权用户权限管理、权限分配和登录行为记录等功能。
11)软件模块化结构设计。
4.2分区计量的建设
4.2.1分区计量区域设计时需考虑的因素
4.2.1.1用水单位类型
在实施供水管网分区管理过程中,由于不同用水单位存在的用水差异,应区别对待。比如工业园区的用水量较为稳定,呈季节性变化特点。住宅小区、公共机构、校园等,不仅随季节性变化,而且会出现每日的早、中、晚用水高峰。要充分考虑不同区域的用水规律,进行区域合理性规划。
4.2.1.2供水压力
资源链接 请先登录(扫码可直接登录、免注册)点此一键登录 ①本文档内容版权归属内容提供方。如果您对本资料有版权申诉,请及时联系我方进行处理(联系方式详见页脚)。
②由于网络或浏览器兼容性等问题导致下载失败,请加客服微信处理(详见下载弹窗提示),感谢理解。
③本资料由其他用户上传,本站不保证质量、数量等令人满意,若存在资料虚假不完整,请及时联系客服投诉处理。
知名地产施工工艺标准图册340页(精装篇)
第二章:精装修工程标准做法汇编
第一节:饰面板(瓷砖/石材)
1、施工工艺 标准
1.1 墙地砖/石材排版
1.1.1 非整砖宜铺贴在两侧阴角或家具下方,单面墙地面不宜有两列非整砖,非整砖的宽度不小于原砖的 1/3;
1.1.2 墙面由阳角开始排砖,阳角和门口两侧必须设整砖,主立面压侧立面,阳面压阴面;
1.1.3 门厅、起居室地面由中间向四周排砖或玄关向沙发位置排砖,厨卫间地面可从一边排砖;
1.1.4 马赛克必须采用背板方式铺贴(采用环氧树脂将马赛克铺贴在背板之上,然后上墙铺贴),转角马赛克尺寸不小于单粒 2/3;
1.1.5 厨卫间无吊顶时,墙面砖距顶棚留约 50mm 宽的平直空隙,具体按模数计算。
1.2 瓷砖/石材面层整体观感
1.2.1 排版合理,无明显大小头;
1.2.2 接缝均匀、深浅一致、周边平直、镶嵌正确,嵌缝连续密实,宽度和深度一致,嵌填平滑;
1.2.3 表面洁净、平整、无磨痕,图案清晰,色泽一致,板块无裂纹、缺损等缺陷,石材表面应无泛碱、变色、污渍等污染;
1.2.4 孔洞套割吻合,边缘整齐;
1.2.5 墙裙、踢脚线等表面洁净、高度一致、结合牢固、出墙厚度一致;
1.2.6 卫生间、阳露台铺装地面坡向正确,无倒坡、积水;
1.2.7 严禁出现非工厂拼贴的 100mm 宽以下天然石材现场拼贴,防止断裂。
1.3 瓷砖/石材色差及加工质量控制
1.3.1 任何一批瓷砖/石材进场时,在空地上铺开 10m²,2m 视线范围内,判断材料是否色差及边角是否存在翘曲的质量问题且对照计划单检查加工尺寸是否准确;
1.3.2 不同批次之间的瓷砖/石材易发生色差问题,建议同一房间的瓷砖,使用同一批次材料;
1.3.3 存在不同批次供货时,需要做好不同批次备货工作,以便后期维修更换;
1.3.4 对不同批次材料的管理,可采取提前知会、甲方合同中限定批次数量、对不同批次做好备货工作等措施;
1.3.5 材料运输过程中,注意瓷砖叠加可能导致的石蜡污染的问题;
1.3.6 为了防止出现外饰面石材颜色不一致,铺贴时应对石材进行认真的挑选和试拼。
1.4 石材地面拼贴
1.4.1 石材拼花地面需在工厂加工完成,水刀切割,图案清晰、色泽一致、接缝均匀、镶嵌正确,花纹对称,加工精细,板块无裂纹、掉脚、缺楞缺陷;
1.4.2 石材在现场切割时,应严格控制锯的行走速度,防止崩茬等现象;
1.4.3 石材地面需采用密封拼贴,拼缝采用同色胶修补,打磨完成后整体进行结晶处理;
1.4.4 石材地面打磨需在木质踢脚线、封口线以及第一遍面涂或壁纸铺贴之前进行;
1.4.5 石材地面存在落地软硬包、木饰面时,需对其墙根进行防潮处理,防止地面打磨导致墙面受潮发霉;
1.4.6 设计无要求时,不同材质的地面面层在分界处嵌入玻璃条或铜条等,使界线分明清晰。
1.5 墙地瓷砖留缝
1.5.1 设计无要求时,墙砖离缝铺贴,墙砖尺寸≤60cm,预留缝隙不小于 0.5mm,墙地砖尺寸超过 60cm 时,预留缝隙不小于 1mm;
1.5.2 如设计无要求,地砖离缝铺贴,预留缝隙 1.5~2 ㎜;
1.5.3 为有效控制离缝宽度,铺贴时必须配合塑料十字卡施工;
1.5.4 墙地砖嵌缝必须采用专用填缝剂,要求填缝饱满,并用挖耳勺收光,缝深 0.5mm,保持光滑。
1.6 石材阳角拼缝
1.6.1 石材阳角采用 45°拼角,铺贴完成后可对拼缝填缝、圆角打磨、抛光处理,禁止采用原边收口;
1.6.2 石材踢脚线采用胶粘成品阳角踢脚线,可视面抛光;
1.6.3 浴缸台面石严禁采用 45°拼角,平面压立面铺贴。 瓷砖阳角拼缝
1.7 瓷砖阳角拼缝
1.7.1 瓷片 45 度斜角,抛光砖 3*3mm 海棠角,防止瓷砖崩角,保证拼缝严密,上下砖的阳角缝顺直;
1.7.2 瓷砖踢脚线阳角同样采用小海棠角(1.5mm),禁止采用原边收口。
1.8 室内地面标高
1.8.1 室内地面须绘制标高索引图,包括结构标高、粘结层及材料层厚度、完成面标高、找坡方向等内容;
1.8.2 厅房地面高于卫生间地面 20mm;
1.8.3 厅房地面宜高于入户花园地面 20mmm;
1.8.4 过廊、客厅及卧室地面统一标高。
1.9 石材/瓷砖地面与木地板地面
1.9.1 木地板与石材/瓷砖地面平接时,需对石材/瓷砖平缝倒角 2mm,木地板需低于石材/瓷砖地面2mm;
1.9.2 当木地板与石材/瓷砖地面留置伸缩缝时,需在接缝设置收口条。
资源链接 请先登录(扫码可直接登录、免注册)点此一键登录 ①本文档内容版权归属内容提供方。如果您对本资料有版权申诉,请及时联系我方进行处理(联系方式详见页脚)。
②由于网络或浏览器兼容性等问题导致下载失败,请加客服微信处理(详见下载弹窗提示),感谢理解。
③本资料由其他用户上传,本站不保证质量、数量等令人满意,若存在资料虚假不完整,请及时联系客服投诉处理。
NB/T 10640-2021 风电场运行风险管理规程
ICs27.180
CCS F11 NB
中华人民共和国能源行业标准
NB/T10640-2021
风电场 运行风险 管理规程
Code for operation risk management of wind farm
2021-04-26发布2021-10-26实施
国家能源局发布
1范围
本文件规定了风电场运行风险评估、管控及改进和记录等要求。
本文件适用于陆上风电场运行的风险管理。
2规范性引用文件
下列文件中的内容通过文中的规范性引用而构成本文件必不可少的条款。其中,注日期的引用文件,仅该日期对应的版本适用于本文件:不注日期的引用文件,其最新版本(包括所有的修改单)适用于本文件。
GB/T23694风险管理术语
GB/T24353风险管理原则与实施指南
GB/T27921风险管理风险评估技术
3术语和定义
GB/T23694界定的术语和定义适用本文件。
4基本规定
4.1风电场应建立风险管理制度,明确风险管理目标和范围,制定风险管理的责任、流程及标准,并根据人员、设备、环境、文化等因素变化,及时完善风险管理制度。
4.2风电场应将风险管理贯穿于生产管理过程中,风险管理应遵循GB/T24353的要求,风险评估方法可按照GBT27921执行.
4.3风电场每年应制定风险管理工作方案,提出风险管理工作实施的只体要求和保障措施。
4.4风电场应通过风险管理将风险控制在可接受的范围内,确保风险应对充分、有效,全员应参与到风险管理活动中,并及时有效沟通。
4.5风电场应建立健全与风险管理相关的技术和资金保障机制,确保风险管理所需的人力、财力和物力。
4.6风电场风险管理应包括风险评估、管控、改进和记录等环节,并应按照“策划、实施、检查、改进”的动态循环模式开展。
4.7相关法律法规、技术标准、运行方式、设备工况、作业环境及气候等发生变化时,风电场应及时对相关风险重新进行评估。
5风险评估
5.1风险识别
5.1.1风电场应开展风险源收集工作,并通过风险识别对风险源的原因和潜在后果进行分析。
5.1.2风电场风险源获应充分考虑自然灾害、事故灾难、社会安全、公共卫生等方面因素,以及生产作业过程中人、物、环境、管理等方面存在的危险和有害因素。
5.1.3风电场风险源获取应通过现场调查、安全检查、安全验收和评估及员工提出意见和建议等方式开展。
资源链接 请先登录(扫码可直接登录、免注册)点此一键登录 ①本文档内容版权归属内容提供方。如果您对本资料有版权申诉,请及时联系我方进行处理(联系方式详见页脚)。
②由于网络或浏览器兼容性等问题导致下载失败,请加客服微信处理(详见下载弹窗提示),感谢理解。
③本资料由其他用户上传,本站不保证质量、数量等令人满意,若存在资料虚假不完整,请及时联系客服投诉处理。
NB/T 10638-2021 光伏发电站能效技术监督规程
ICs27.160
CCS F 12 NB
中华人民共和国能源行业标准
NB/T10638-2021
光伏发电站 能效技术 监督规程
Technology supervision code of energy efficiency performance for photovoltaic power station
2021-04-26发布2021-10-26实施
国家能源局发布
1范围
本文件规定了光伏发电站在设计选型、安装调试、运行、检修阶段的能效技术监督要求。
本文件适用于大、中型光伏发电站。
2规范性引用文件
下列文件中的内容通过文中的规范性引用而构成本文件必不可少的条款,其中,注日期的引用文件,仅该日期对应的版本适用于本文件:不注日期的引用文件,其最新版本(包括所有的修改单)适用于本文件。
GBT30427并网光伏发电专用逆变器技术要求和试验方法
GBT35694光伏发电站安全规程
GB/T36567光伏组件检修规程
GBT36568光伏方阵检修规程
GBT38330光伏发电站逆变器检修维护规程
GBT38335光伏发电站运行规程
GB50794光伏发电站施工规范
GB50796光伏发电工程验收规范
GB50797光伏发电站设计规范
NB/T10113光伏发电站技术监督导则
NBT10634光伏发电站支架及跟踪系统技术监督规程
NB/T10635光伏发电站光伏组件技术监督规程
NB/T10636光伏发电站逆变器及汇流箱技术监督规程
NB/T32012光伏发电站太阳能资源实时监测技术规范
NB/T32032光伏发电站逆变器效率检测技术要求
NB/T32034光伏发电站现场组件检测规程
3术语和定义
GBT36567、GBT36568、GB/T38335、GB/T38330、NB/T10113界定的以及下列术语和定义适用于本文件。
能效监督energy conservation supervision
采用技术手段或措施,对光伏发电站在设计选型、安装调试、运行、检修过程中涉及电站发电性能的项目、内容进行监督和管理的活动。
4总则
4.1光伏发电站能效技术监督的原则、机构和管理要求应符合NBT10113的规定。
4.2光伏发电站能效技术监督内容主要包括:
a)设计选型阶段电站选址、太阳能资源、阵列间距、设备性能要求等方面的监督;
b)安装调试阶段设备到货验收、安装要求、能效测试、资料审查等方面的监督;
c)运行阶段电站运行程、巡检要求、指标统计、运行分析等方面的监督;
d)检修阶段电站检修规程、检修周期、检修项目、能效测试等方面的监督。
4.3光伏发电站能效技术监督应有工作计划、过程记录、故障消除记录等技术资料,形成闭环管理。
4.4光伏发电站能效技术监督应符合GB/T35694的安全要求。
4.5光伏发电站宜结合设备运行状态每年至少开展一次能效技术监督的检查、评价工作。
资源链接 请先登录(扫码可直接登录、免注册)点此一键登录 ①本文档内容版权归属内容提供方。如果您对本资料有版权申诉,请及时联系我方进行处理(联系方式详见页脚)。
②由于网络或浏览器兼容性等问题导致下载失败,请加客服微信处理(详见下载弹窗提示),感谢理解。
③本资料由其他用户上传,本站不保证质量、数量等令人满意,若存在资料虚假不完整,请及时联系客服投诉处理。
NB/T 10637-2021 光伏发电站监控及自动化技术监督规程
ICS27.160
CCS F 12 NB
中华人民共和国能源行业标准
NB/T10637-2021
光伏发电站 监控及自动化技术 监督规程
Technology supervision code of monitoring control and automation for photovoltaic power station
2021-04-26发布2021-10-26实施
国家能源局发布
1范围
本文件规定了光伏发电站监控及自动化系统的设计选型、安装调试、运行及检修维护等方面的技术监督要求。
本文件适用于大、中型光伏发电站。
2规范性引用文件
下列文件中的内容通过文中的规范性引用而构成本文件必不可少的条款。其中,注日期的引用文件,仅该日期对应的版本适用于本文件:不注日期的引用文件,其最新版本(包括所有的修改单)适用于本文件。
GBT19964光伏发电站接入电力系统技术规定
GBT28448信息安全技术网络安全等级保护测评要求
GB/T30153光伏发电站太阳能资源实时监测技术要求
GB/T31366光伏发电站监控系统技术要求
GBT33599光伏发电站并网运行控制规范
GB/T35694光伏发电站安全规程
GB/T38335光伏发电站运行规程
GB50174数据中心设计规范
GB50348安全防范工程技术标准
GB50394入侵报警系统工程设计规范
GB50395视频安防监控系统工程设计规范
GB50396出入口控制系统工程设计规范
GB50794光伏发电站施工规范
GB50797光伏发电站设计规范
DLT381电子设备防雷技术导则
DLT516电力调度自动化系统运行管理规程
DLTT24电力系统用蓄电池直流电源装置运行与维护技术规程
DLT1074电力用直流和交流一体化不间断电源
DLT1100.1电力系统的时间同步系统第1部分:技术规范
DLT1404变电站监控系统防止电气误操作技术规范
DLT1941可再生能源发电站电力监控系统网络安全防护技术规范
DL/T5149变电站监控系统设计规程
DLT5344电力光纤通信工程验收规范
NBT10113光伏发电站技术监督导则
NB/T32011光伏发电站功率预测系统技术要求
NBT32012光伏发电站太阳能资源实时监测技术规范
3术语和定义
GB/T31366、NBT10113界定的术语和定义适用于本文件。
4总则
4.1光伏发电结监控及自动化技术监督的原则、机构和管理要求应符合NBT10113的要求。
4.2光伏发电站监控及自动化技术监督的范围包括:
a)监控系统;
b)功率预测系统;
c)太阳跟踪系统;
d)太阳能资源观测站;
e)入侵报警系统、视频安防系统、出入口控制系统、火灾自动报警系统等。
4.3光伏发电站监控及自动化技术监督的阶段包括:
a)设计选型监督;
b)安装调试监督;
c)运行监督;
d)检修维护监督。
4.4光伏发电站监控及自动化系统的设计选型、安装调试、运行及检修锥护应符合GB/T35694的安全要求。
4.5光伏发电站宜结合设备运行状态每年至少开展一次监控及自动化系统的技术监督检查、评价工作。
4.6光伏发电站监控及自动化系统的设计选型、安装调试、运行及检修维护应有工作计划、过程记录、故障消除记录等技术资料,形成闭环管理。
资源链接 请先登录(扫码可直接登录、免注册)点此一键登录 ①本文档内容版权归属内容提供方。如果您对本资料有版权申诉,请及时联系我方进行处理(联系方式详见页脚)。
②由于网络或浏览器兼容性等问题导致下载失败,请加客服微信处理(详见下载弹窗提示),感谢理解。
③本资料由其他用户上传,本站不保证质量、数量等令人满意,若存在资料虚假不完整,请及时联系客服投诉处理。
知名地产施工工艺标准图册340页(土建篇)
总说明
一、为促进越秀地产建设工程项具质量水平鰲体提高,提升育户满意度,降低质量成杰,创造精品工程打造企业品牌,特编制本图册。
本图册作为越秀地产工艺标准图集,包括土建工程、精装修工程、防渗漏体系、安装工程、成品保护五大部分。
本图册为越秀地产统一标准,将作为设计、招标、施工、成本结算的依据,供越秀地产项目设计、施工、监理等单位在全地产公司使用。同时,本图册也是对本企业质量管理监督、检查和评价的依据各辖下地产公司必须严格执行;由于各地区、项目差异,各辖下地产公司可自行统一标准执行;对于图册内有多个方案的,各辖下地产公司可自行根据当地施工队伍习惯及水平选择相应方案,方案选择要在设计前确定。
除执行本图册标准外,还应执行国家现行有关标准、规范的规定,如本图册标准与国家现行有关标准、规范的规定有冲突时,按国家现行有关标准、规范的规定执行。
如本图册标准与项目设计不一致的,以设计为准。但设计前应与设计方充分沟通,原则上要求设计与本图册施工工艺 标准应相一致。
二、应用范围:越秀地产全系列产品开发项目。
三、本图册自发布之日起生效,越秀地产招投标中心负责咨询和解释。
第一章:土建工程标准做法汇编
第一节:钢筋工程
1、施工工艺标准
1.1钢筋连接
1.1.1滚轧直螺纹套筒连接
(1)钢筋下料
钢筋下料用砂轮切断机,不准用气割。钢筋下料尺寸按施工图要求,钢端头面垂直于钢筋轴线,端头禁止挠曲或出现马蹄形。
(2)钢筋套丝
钢筋套丝可以在钢筋加工场进行预制。
(3)安装塑料保护帽及连接套
加工过程中用通、止环规逐个检查套丝牙形并利用塑料帽检查锥形端加工质里。对达到质里要求的丝头,拧上塑料保护帽,并按规定的力矩值拧上连接套。
1.1.2电渣压力焊
(1)作业条件
a.钢筋端部的调直和清理:钢筋端部弯曲的要调直,调直不了的须切除,端头歪斜变形大的也应切除。钢端部2m长范围内应把泥砂、扶锈、油渍等污垢清除干净。
b.焊工已经有关部门培训、考核合格,持证上岗。上岗时,应穿戴好焊工鞋,焊工手套等劳动保护用品。
c.电源线路已架设到工作面,电压正常。焊机、控制系统路已连接好,工作状态正常。
d.根据上钢筋长度,搭设符合要求的相应操作平台及防护脚手架,以供辅助工扶直钢筋之用。
e.在焊接施工前,应根据焊接钢筋直径的大小,参考下表选定电渣压力焊的工作参数。在施焊前,先做焊接试验,以确定工艺参数,制三个拉伸试件,试验合格后方能正式施焊。
资源链接 请先登录(扫码可直接登录、免注册)点此一键登录 ①本文档内容版权归属内容提供方。如果您对本资料有版权申诉,请及时联系我方进行处理(联系方式详见页脚)。
②由于网络或浏览器兼容性等问题导致下载失败,请加客服微信处理(详见下载弹窗提示),感谢理解。
③本资料由其他用户上传,本站不保证质量、数量等令人满意,若存在资料虚假不完整,请及时联系客服投诉处理。
NB/T 10635-2021 光伏发电站光伏组件技术监督规程
ICs27.160
CCS F 12 NB
中华人民共和国能源行业标准
NB/T10635-2021
光伏发电站 光伏组件 技术监督规程
Technology supervision code of photovoltaic modules for photovoltaic power station
2021-04-26发布2021-10-26实施
国家能源局发布
1范围
本文件规定了光伏发电站光伏组件设计选型、安装调试、运行维护及检修等方面的技术监督要求。
本文件适用于大中型光伏发电站。
2规范性引用文件
下列文件中的内容通过文中的规范性引用而构成本文件必不可少的条款。其中,注日期的引用文件,仅该日期对应的版本适用于本文件:不注日期的引用文件,其最新版本(包括所有的修改单)适用于本文件。
GBT2828.1计数抽样检验程序第1部分:按接收质量限(AQL)检索的逐批检验抽样计划
GB/T6495.1光伏器件第1部分:光伏电流-电压特性的测量
GB/T6495.9光伏器件第9部分:太阳模拟器性能要求
GB/T9535地面用品体硅光伏组件设计鉴定和定型
GB/T18210品体硅光伏(PV)方阵I-V特性的现场测量
GB/T189I】地面用薄膜光伏组件设计鉴定和定型
GB/T35694光伏发电站安全规程
GB/T36567光伏组件检修规程
GB/T38335光伏发电站运行规程
GB50794光伏发电站施工规范
GB/T50796光伏发电工程验收规范
GB50797光伏发电站设计规范
NBT10113光伏发电站技术监督导则
NBT32034光伏发电站现场组件检测规程
3术语和定义
GBT9535、GB/T35694、GB/T38335、GB50797、NB/T10113界定的术语和定义适用于本文件。
4总则
4.1光伏发电站光伏组件技术监督的原则及机构应符合NBT10113的要求。
4.2光伏发电站光伏组件的技术监督内容包括多品硅光伏组件、单品硅光伏组件和薄膜光伏组件。
4.3光伏发电站光伏组件的技术监督阶段包括:
a)设计选型监督。
b)安装调试监督。
c)运行维护监督。
d)检修监督。
4.4光伏发电站光伏组件的安装调试、运行维护及检修应有工作计划、过程记录、故障消除记录等技术资料,形成闭环管理。
4.5光伏组件的调试、运行维护、检修过程中的安全应符合GB/T35694的要求。
资源链接 请先登录(扫码可直接登录、免注册)点此一键登录 ①本文档内容版权归属内容提供方。如果您对本资料有版权申诉,请及时联系我方进行处理(联系方式详见页脚)。
②由于网络或浏览器兼容性等问题导致下载失败,请加客服微信处理(详见下载弹窗提示),感谢理解。
③本资料由其他用户上传,本站不保证质量、数量等令人满意,若存在资料虚假不完整,请及时联系客服投诉处理。
DL/T 5835-2021 水电水利工程施工机械安全操作规程 沥青混凝土摊铺机
ICS27.140
CCS P59 DL
中华人民共和国电力行业标准
DL/T5835-2021
水电水利工程 施工机械安全操作规程 沥青混凝土摊铺机
Safety operation code for construction equipment of hydropower and water conservancy engineering
Asphalt concrete paver
2021-04-26发布2021-10-26实施
国家能源局发布
1总则
1.0.1为规范水电水利工程沥青混凝土摊铺机安全操作行为,保障人员和设备的安全,制定本规程。
1.0.2本规程适用水电水利工程中沥青混凝土摊铺机的安全操作。
1.0.3沥青混凝土摊铺机作业还应符合现行行业标准《水电水利工程土建施工安全技术规程》DL/T5371、《水电水利工程施工作业人员安全操作规程》DLT5373的有关规定。
1.0.4沥青混凝土推铺机作业除应符合本规程外,尚应符合国家和行业有关标准的规定。
2术语
2.0.1沥青混凝土摊铺机asphalt concrete paver
将沥青混合料均匀摊铺开,并进行初步振实和整平的机械。按行走方式分为拖式和自行式,其中自行式又分为履带式和轮胎式。
2.0.2刮板输送装置scraper conveyer
由刮板输送链实现将料斗中的混合料向后输送到沥青混凝土摊铺机螺旋料槽中的装置。
2.0.3螺旋分料装置screw conveyer
将沥青混合料均匀分布在熨平装置前方的螺旋输送器。
2.0.4熨平装置screeding unit
由牵引臂牵引,按预定的施工宽度、厚度和拱度要求,将螺旋输送器分布好的沥青混合料进行摊铺、初夯、熨平的装置。按宽度延宽方式分为机械拼装式和液压伸缩式。
2.0.5自动调平系统auto leveling system
由基准、自动调平控制器和液压执行机构等组成的系统,可以自动调节左右牵引臂前端牵引点的高度,保持熨平装置纵向与横向倾角为设定值,达到摊铺作业面纵横向平整的要求。3安装与拆除
3.1一般规定
3.1.1安装、拆除前应根据设备技术文件、相关安全法规等有关规定,结合现场实际编制专项方案,专项方案至少应包括以下内容:
1安装与拆除准备工作。
2施工人员、材料与设备配置及场地要求。
3施工进度计划。
4安装与拆除的施工方法及工艺要求。
5安装与拆除注意事项。
6安全技术措施及应急预案等。
3.1.2安装、拆除前,应对参与安装和拆除工作的人员进行安全培训和技术、安全交底,做好交底记录。
3.1.3从事安装与拆除工作的特种作业人员应持证上岗,并穿戴安全防护用品。
3.1.4安装、拆除前,应组织对沥青混凝土摊铺机的各部件、液压与电气系统进行检查,并做好记录。
3.1.5安装、拆除前应保证沥青混凝土摊铺机的发动机及电源等动力装置处于关闭状态。
3.1.6安装和拆除作业前应检查起吊设备和吊具的符合性、完好性。
3.1.7起吊作业应执行现行国家标准《起重机械安全规程》GB6067的规定。起钩前,应确认该部件已解除连接,不得使用起吊工具强行分离;脱钩前,应检查已就位部件是否稳定和安全。
3.2安装与调试
3.2.1沥青混凝土摊铺机安装应按照专项方案实施,并做好记录。
3.2.2沥青混凝土摊铺机安装应包含延宽熨平装置、螺旋分料装置及电气元件等,其中电气元件安装应包括远控盒安装、料位传感器安装、调平仪安装。
3.2.3安装完成后,应按设备厂家的技术文件进行调试,调试应包括行驶、刮板输料、螺旋分料、自动调平、集中润滑、电气控制等。
3.2.4用于摊铺沥青混凝土心墙时,还应调试过渡料调节板。
3.2.5沥青混凝土摊铺机调试合格后方可投入使用。
3.3拆除
3.3.1沥青混凝土摊铺机拆除应按照专项方案实施,并做好记录。
3.3.2拆除时宜以厂家出厂部件为拆除单元。
3.3.3拆除后的仪器、仪表及电气元件,应有防震、防水、防雷击等保护措施。
3.3.4收工拆除时应将远控盒、料位传感器、自动调平仪等电气元件临时拆除。
3.3.5转场拆除时应将延宽熨平装置、螺旋分料装置及电气元件等拆除。
3.3.6所有部件应进行检查、检修与保养,所有运转部位应进行清洗、注油,裸露结合部位应进行包扎保护。
3.3.7拆除完毕后,所有部件、配件应按要求分类堆放整齐,妥善保管。
4运行
4.1一般规定
4.1.1作业人员应经过专业培训,并考核合格后上岗,施工前应进行安全技术交底。
4.1.2未经允许,不得对沥青混凝土摊铺机进行任何改装、擅自加装或拆除任何部件或设施。
4.1.3沥青混凝土摊铺机的安全保护装置和安全警示装置应齐全、可靠。配备有效的消防器材或消防设施。
4.1.4与摊铺作业相关的道路、动力供应、照明设施、安全设施、牵引设施等环境条件均应满足施工要求。
4.1.5沥青混凝土摊铺机作业中不得超温、超速、超压、超载运行。运行中发现异常现象,应立即停机检查,故障排除后方可继续使用。
4.1.6装有延宽熨平装置的沥青混凝土摊铺机自行转场时,应在料斗内加装配重,并升起熨平装置,用挂钩挂牢。转场距离超过1km时应使用拖车运输。
4.2作业前准备
4.2.1摊铺前应进行以下准备工作:
1检查沥青混凝土摊铺机的设备状况及周围环境情况。
2应根据铺筑的宽度、厚度等施工要求,安装电气元件,调整熨平装置仰角等参数。
3将所有操纵杆、开关、电位器旋钮置于中位,油门操纵杆放置在怠速位置。
4接触沥青混合料的设备部位应均匀喷酒少量脱模剂,如接料斗、顶推滚轮、刮板输送器、螺旋分料器、行走传动链、熨平板及底板等部位。
5熨平板下落前,应在熨平板下垫与摊铺厚度相同的木板。
6摊铺沥青混凝土心墙时还应调整框模宽度。检查侧模板与框模的连接情况是否正常,框模与过渡料斗的连接弹簧是否正常。
4.2.2沥青混凝土摊铺机启动应按下列要求进行:
1接通电控系统的主电源,观察显示器状态,若有异常应及时排除。
2启动前,应确认设备内外部无障碍物后,鸣笛发出警示信号。
3启动后,松开点火开关,观察显示器指示是否正常,是否存在异常声响。冷车启动后应先怠速预热不少于3mi,待发动机各部温度正常后方可工作。
4初次启动不成功,再次启动前,应先将钥匙转到关闭位置后再进行启动。每次启动持续时间不得超过10$,启动间隔时间不少于1min。连续三次不能启动的,应查明原因,排除故障后方能再启动。
4.2.3熨平板预热时应符合以下要求:
1对熨平板进行预热,使其接近沥青混合料的摊铺温度。
2燃油或燃气加热装置火焰熄灭应立刻关闭开关,排除故障并清除溢出的燃油或待燃气排尽后重新点燃。
3电加热装置加热前,应对加热系统的电气线路进行检查。
4熨平板在加热过程中,应有专人监管,防止局部过热导致变形现象,不得向设备各部件喷油清洗。
资源链接 请先登录(扫码可直接登录、免注册)点此一键登录 ①本文档内容版权归属内容提供方。如果您对本资料有版权申诉,请及时联系我方进行处理(联系方式详见页脚)。
②由于网络或浏览器兼容性等问题导致下载失败,请加客服微信处理(详见下载弹窗提示),感谢理解。
③本资料由其他用户上传,本站不保证质量、数量等令人满意,若存在资料虚假不完整,请及时联系客服投诉处理。
知名地产防渗防裂节点构造标准图集
防渗防裂节点构造标准
说 明
一、《防渗防裂 节点构造 标准》是集团股份有限公司企业标准之一,共有地下工程防渗防裂节点 构造标准、屋面工程防渗防裂节点构造标准、外墙工程防渗防裂节点构造标准、楼地面工程防渗防裂 节点构造标准、外墙门窗工程安装防渗漏节点构造标准、砌体防开裂节点构造标准和给排水管道及卫生洁具安装工程防渗漏节点构造标准7个部分,为推荐性标准图集。其编写目的是为设计部、工程部工程技术人员提供较为有效的防渗防裂 做法和相关的质量控制要点。
二、本《防渗防裂节点构造标准》由集团工程管理部根据集团各项目及标杆企业的经验编制,具有较 强的实用性和可操作性,可以指导施工图纸的设计和现场施工,各公司设计部、工程部可以根据本项目具体情况选择适合的节点标准作为设计任务书的要求及招标文件的技术要求,同时,本标准也可作为工程部编制项目《防渗防裂专项施工方案》的依据。
三、编制依据:
1、《地下工程防水技术规范》 GB50108-2008
2、《地下防水工程质量验收规范》 GB50208-2011
3、《屋面工程技术规范》 GB50345-2012
4、《屋面工程质量验收规范》 GB50207-2012
5、《种植屋面工程技术规程》 JGJ155-2013
6、《建筑地面设计规范》 GB50037-2013
7、《建筑地面工程施工质量验收规范》 GB50209-2010
8、《建筑装饰装修工程质量验收规范》 GB50210-2011
9、《建筑工程施工质量验收统一标准》 GB50300-2013
10、《砌体结构工程施工质量验收规范》 GB50203-2011
11、《住宅设计规范》 GB50096-2011
12、《住宅建筑规范》 GB50368-2005
13、《建筑给排水及采暖工程施工质量验收规范》 GB50242-2002
14、《建筑给排水硬聚氯乙烯管道工程技术规程》 CJJ/T29-2010
15、《自动喷水灭火系统施工及验收规范》 GB50261-2005
16、《建筑给水聚乙烯管道工程技术规程》 CJJ/T98-2003
17、《建筑给水聚丙烯管道工程技术规程》 GB/T50349-2005
18、《通风与空调工程施工质量验收规范》 GB50243-2016
四、本标准中的防水层材料仅供参考,各项目可以根据本地区具体情况作出修改,以设计图纸为准,本标准主要是提供节点的构造做法。
五、本《防渗防裂节点构造标准》由集团工程总监审核、总裁批准后正式发布。
目录
一、地下室渗漏节点做法
总体要求··························································1
地下室底板防水构造详图·············································2
底板沉降后浇带超前止水节点构造图···································2
地下室与地下室出入口连接处底板防水构造·····························3
地下室与地下室出入口连接处墙体防水构造·····························3
地下室外墙后浇带防渗漏大样图·······································4
地下室顶板后浇带节点构造简图·······································4
地下室顶板转角(阳角)部位节点构造简图·····························5
外墙转角(阳角)构造节点简图·······································5
地下室种植顶板(防水等级一级)构造图·······························6
旭辉建造 2·0 后浇带盖板穿插施工····································6
地下室外墙防水构造简图·············································7
覆土以下外墙止水螺杆节点构造简图···································7
外墙穿墙预埋套管(平墙面)节点构造简图·····························8
地下室排风井道大样·················································8
消防电梯基坑和排水基坑做法·········································9
无水电梯基坑做法···················································9
地下室顶板转角高墙(阴角)部位节点构造简图························10
种植屋面暗沟方式排水大样··········································10
灌注桩桩头防水节点················································11
抗拔桩桩头防水节点················································11
外墙穿墙预埋群套管(凸出墙面)节点构造简图························12
外墙穿墙预埋群套管(平墙面)节点构造简图··························12
地下室排水沟······················································13
地下室顶板车辆坡道················································13
外墙穿墙预埋管节点构造简图········································14
出顶板面立管节点构造简图··········································14
设备机房排水地沟··················································15
汽车坡道排水地沟··················································15
二、屋面防渗漏节点做法
总体要求·························································16
出屋面烟风道防水构造节点做法(平屋面)······························17
出屋面烟风道防水构造节点做法(坡屋面)······························18
屋面排气帽构筑节点················································19
屋面排水檐口防渗漏节点做法········································19
屋面彩瓦与女儿墙及构筑墙体构筑节点································20
水泥屋面瓦体系节点(天沟)··········································21
斜屋面彩瓦避雷引下线及避雷支架防渗漏节点··························22
坡屋面檐沟防渗漏节点··············································23
屋面墙体交界处构造(水泥瓦屋面体系)································24
平屋面屋顶构造图··················································25
平屋面屋露台顶构造图··············································25
平屋面屋露台和室内顶构造图········································26
出屋面反坎构造图··················································26
屋面变形缝构造做法················································27
屋面侧排式落水斗防渗漏节点做法····································28
屋面排水地漏防渗漏节点做法········································28
屋面女儿墙(1)防渗漏节点做法 ····································29
屋面女儿墙(2)防渗漏节点做法·····································29
屋面保温通气管····················································30
出屋面设备管立管根部节点··········································31
天沟防渗漏节点····················································32
斜屋面模板体系····················································33
风井出屋面详图····················································34
三、外墙防渗漏节点做法
总体要求 ························································35
伸缩、抗震、沉降缝渗漏节点做法 ···································36
凸出外墙面装饰线条节点做法········································37
外墙螺杆孔洞 ·····················································38
混凝土外墙空调、新风、排气、排烟洞节点做法························39
卫生间通气孔洞节点做法 ···········································40
采光井玻璃屋顶节点做法 ···········································41
外墙保温板框点粘贴节点 ···········································42
外墙雨阳棚节点构造 ··············································43
回土面一下必须混凝土浇筑墙体加防水节点做法 ·······················43
阳露台壁灯、遮阳预埋安装节点做法 ·································44
单体排水沟节点做法················································45
单体入大堂及别墅人户节点做法······································46
外墙楼梯踏步及开放式楼梯节点做法 ·································47
消防连廊防水节点做法 ·············································48
外墙空调板加强防水节点构造 ·······································48
外墙飘窗防水节点构造··············································49
四、楼地面防渗漏节点做法
总体要求 ························································50
淋浴房挡水条及门槛石节点做法······································51
卫生间电地暖、客厅水地暖节点做法··································52
厨房间电地暖、客厅水地暖节点做法 ·································53
阳台客餐厅(铝合金)移门防水及标高做法····························54
阳台客餐厅(塑钢)移门防水及标高做法 ·····························55
卫生间门槛节点做法················································56
厨房间门槛节点做法 ···············································57
阳台和客餐厅防水及标高构造········································58
卫生间干湿分离节点做法 ···········································59
水地暖进卫生间节点做法 A··········································60
水地暖进卫生间节点做法 B ·········································61
客餐厅地暖施工,卫生间无地暖做法 ·································62
客餐厅地暖施工,厨房间无地暖做法··································63
卫生门线条和门槛石节点做法 ·······································64
厨房间门线条和门槛石节点做法 ·····································65
浴缸安装节点做法一 ··············································66
浴缸安装节点做法二 ··············································67
浴缸安装节点做法三 ··············································68
坐便器安装 ······················································69
台盆下水安装节点做法一 ··········································70
台盆下水安装节点做法二 .··········································71
厨房下水安装节点做法 ············································72
地漏及止水节节点做法 ············································73
预留管洞穿楼板防渗漏节点做法 ····································74
排水管立管止水节防渗漏节点做法 ···································75
煤气立管、消防立管、给水立管防渗漏节点做法 ·······················76
同层排水沉箱防渗漏节点做法 ······································77
卫生间防水节点做法 ·············································78
五、外墙门窗防渗漏安装节点做法
总体要求 ·······················································79
平开窗(含副框)标准安装节点 ····································80
平开窗(厨卫间)标准安装节点 ····································81
平开窗标准安装节点 ··············································82
平开窗悬窗(厨卫间)标准安装节点 ································83
裙房平开窗(厨卫间)标准安装节点 ································84
推拉窗(含副框毛坯)标准安装节点 ································85
推拉窗(含副框精装修厨卫间)标准安装节点 ························86
推拉窗标准安装节点 ··············································87
推拉窗标准安装节点 ··············································88
裙房平开窗(厨卫间)标准安装节点 ································89
平开窗(含副框)标准安装节点 ····································90
平开窗(厨卫间)标准安装节点 ····································91
推拉窗标准安装节点 ·············································92
推拉窗标准安装节点 ··············································93
裙房平开窗(厨卫间)标准安装节点 ································94
推拉窗(含副框毛坯)标准安装节点 ································95
推拉窗(含副框精装修厨卫间)标准安装节点 ························96
推拉窗标准安装节点 ··············································97
裙房平开窗(厨卫间)标准安装节点 ································98
推拉窗标准安装节点 ··············································99
PC 预制门窗移门和平开门安装节点 ································100
推拉窗标准安装节点 ·············································101
推拉窗标准安装节点 ·············································102
推拉窗标准安装节点 ·············································103
裙房平开窗(厨卫间)标准安装节点 ·······························104
推拉窗标准安装节点 ·············································105
推拉窗标准安装节点 ·············································106
推拉窗标准安装节点 ·············································107
裙房平开窗(厨卫间)标准安装节点 ·······························108
系统天窗防渗漏安装构造节点一 ···································109
系统天窗防渗漏安装构造节点二 ···································110
铝合金门窗拼角注胶防渗漏做法一 ·································111
铝合金门窗拼角注胶防渗漏做法二 ·································112
铝合金门窗拼角防渗漏做法 ·······································113
铝合金门窗拼角防渗漏做法 ·······································114
六、砌体工程防开裂节点做法;
总体要求 ·······················································115
导墙和给水管预留预埋节点做法 ···································116
外墙洞口构造 ···················································117
入户门洞口 ······················································118
斜砌端部预制混凝土三角块 ········································119
斜砌管线部位节点 ···············································119
斜砌中部预制三角混凝土块 ·······································119
叠合板防开裂做法 ···············································120
七、给排水管道及卫生洁具安装防渗漏节点做法:
总体要求: ·····················································121
卫生间马桶登高管和三角阀及龙头安装防渗漏做法 ····················122
UPVC 排水管消防喷淋管接头安装防渗漏做法 ·······················123
PP-R 管连接防渗漏做法 ··········································124
空调供回水管安装固定支架、空调风管防结露做法 ···················125
给水管道预留槽及后开槽做法 ······································126
柜体内水管凸出墙体做法 ·········································127
低温热水地板辐射供暖系统施工安装(一) ·························128
低温热水地板辐射供暖系统施工安装(二) ·························129
地热分集水器做法 ··············································130
屋面防渗漏节点做法
总体要求
一、本地下工程防渗漏节点做法是在严格执行《地下防水工程质量验收规范》(GB50208一2011)
和《地下工程防水技术规范》(GB50108-2008)的基础上,统一地下工程防水工程中各重点部位的防水细部做法,以规范施工,达到防止渗漏的目的。
二、地下防水工程中涉及的混凝土强度等级、抗渗等级、防水做法必须符合设计图纸的要求。
三、地下防水工程施工前,项目技术负责人必须组织技术人员进行图纸会审,掌握工程主体及细部构造的防水技术要求,并编制防水工程的施工方案。
四、防水混凝土应连续浇筑,宜少留施工缝。当必须留设施工缝时应遵守下列规定:
1、墙体水平施工缝不应留在剪力与弯矩最大处或底板与侧墙的交接处,应留在高出底板表面不小于300mm的墙体上。拱(板)墙结合的水平施工缝宜留在拱(板)墙接缝线以下150-300mm处,墙体
有预留孔洞时施工缝距孔洞边缘不应小于300m。
2、外墙垂直施工缝应避开地下水和裂隙水较多地段,并宜与变型缝相结合。
五、施工缝的施工应符合下列规定:
1、水平施工缝浇灌混凝土前应将其表面浮浆和杂物清除,然后铺设净浆或涂刷混凝土界面处理剂、水泥基渗透结晶型防水涂料,再铺30-50m厚同强度去石子混凝土,并应及时浇灌混凝土。
2、垂直施工缝浇灌混凝土前,应将其表面清理干净,再涂刷混凝土界面处理剂或水泥基渗透结晶型防水涂料,并应及时浇灌混凝土。
3、选用的遇水膨胀止水条应具有缓胀性能,其7的膨胀率不应大于最终膨胀率的60%,最终膨胀率宜大于220%
4、适水膨胀止水条宜牢固地安装在预留槽内。
5、采用中埋式止水带时应确保位置准确,并固定牢靠。
六、防水混凝土结构内部设置的各种钢筋或绑扎铁丝,不得接触模板,用于固定模板的螺栓必须穿过混凝土结构时可采用工具式螺栓或螺栓加堵头,螺栓上应加焊止水环。拆模后将留下的凹槽用密封材料封堵密实,并应聚合物水泥砂浆抹平。
七、防水混凝土终凝后应立即进行养护,养护时间不得少于14。
八、防水混凝土的冬期施工应符合下列规定:
1、混凝土入模温度不应低于50C。
2、混凝土应采用综合蓄热法、蓄热法、暖棚法、摻化学外加剂等养护方法,不得采用电热法或蒸汽直接加热法。
3、应采取保温保湿措施。
九、收缩型后浇带一般在两侧混凝土龄期达到42后施工,沉降型后浇带则必须待高层部位主体结构施工结束、沉降基本完成后浇筑。后浇带应设在受力和变形较小的部位。后浇带应采用补偿收缩混凝土浇筑,其抗渗和抗压等级不应低于两侧混凝土。
资源链接 请先登录(扫码可直接登录、免注册)点此一键登录 ①本文档内容版权归属内容提供方。如果您对本资料有版权申诉,请及时联系我方进行处理(联系方式详见页脚)。
②由于网络或浏览器兼容性等问题导致下载失败,请加客服微信处理(详见下载弹窗提示),感谢理解。
③本资料由其他用户上传,本站不保证质量、数量等令人满意,若存在资料虚假不完整,请及时联系客服投诉处理。
DL/T 5833-2021 水电水利工程施工机械安全操作规程 自动火焰切割机
ICS27.140
CCS P59 DL
中华人民共和国电力行业标准
DL/T5833—2021
水电水利工程 施工机械安全操作规程 自动火焰切割机
Safety operation code for construction equipment in hydroelectric and hydraulic engineering
Automatic flame cutting machine
2021-04-26发布2021-10-26实施
国家能源局发布
1总则
1.0.1为规范水电水利工程自动火焰切割机的安全操作,制定本规程。
1.02本规程适用于水电水利金属结构制造安装工程,不适用于有色金属及设备改造修理热切割加工。
1.0.3自动火焰切割机的安全操作除应遵守本规程外,尚应符合国家现行有关标准的规定。
2术语
2.0.1火焰切割机 flame cutting machine
利用氧气配燃气或燃油进行金属材料切割的设备。
2.0.2数控切割机CNC cutting machine
由数字程序控制进行复杂形状连续自动高精度热切割的机电一体化设备。
2.0.3仿形切割机shape cutting machine
由精密机械传动、电动机驱动割炬沿工件模型外轮廓运动,可对复杂形状进行连续自动仿真切割的自动化热切割设备。
2.0.4管道自动火焰切割机automatic pipe flame cutting machine
火焰切割机自动环绕钢管,连续完成全位置火焰热切割的自动切割设备。
3基本规定
3.0.1凡从事操作的作业人员,应经培训考核合格,持证上岗。
3.0.2作业人员应穿戴好工作服、手套、眼镜等防护用品,遵守安全操作规程和规章制度。
3.0.3氧气间、燃气间宜独立设置,不满足安全间距要求时应按规定封闭隔离。
3.0.4氧气瓶、燃气瓶应按规定进行检验并标识明确。
3.0.5风力大于3级时的露天作业应设挡风屏。风力大于5级或下雨天不得进行露天作业。
3.0.6冬季管路、阀门、割炬冻结时,不得火烤,应使用40℃以下的温水解冻。
3.0.7应对处于阳光曝晒之下的气罐(瓶)、汇流阀、管路进行遮挡。
3.0.8自动火焰切割机的操作还应符合《焊接与切割安全》GB9448、《水电水利工程施工通用安全技术规程》DL/T5370、《水电水利工程金属结构与机电设备安装安全技术规程》DLT5372、《水电水利工程施工作业人员安全操作规程》DL/T5373的规定。
4安装与调试
4.1气站
4.1.1自动火焰切割宜采用集中供气形式,汇流输出总管应设置单向阀。
4.1.2气站的气罐、汇流阀等设备、设施安装施工完成后,应进行检验验收。
4.1.3氧气瓶、燃气瓶不得混放。氧气、燃气库房内不得存放其他易燃、易爆物品。
4.1.4气站及切割现场应设消防设施。
4.1.5气站及其管路安装前应向当地监管部门报备,施工完成后应经其检查、验收。
4.2管路
4.2.1管路宜采用架空敷设,也可采用直接埋地敷设,不得在封闭的地沟中敷设。管路应有可靠的防雷、接地、防静电措施。
4.2.2输送氧气、燃气的管路应用不同颜色区分,且与橡胶软管的颜色保持一致,管件接头严密,管身不得有鼓包、破裂、漏气现象。
4.2.3燃气管路应有防回火装置,每次使用前对其进行检查,保证其处于正常工作状态。
4.2.4每一把割炬应有一个独立的回火防止器。当一根燃气管向多个割炬供气时,总管路及支管路均应安装回火防止器。
4.2.5管路中配置的回火防止器应垂直放置,阻火元件应保持气路畅通。
4.2.6氧气、燃气的橡胶软管不得混用。单根橡胶软管长度不宜小于10m。
4.3切割机
4.3.1切割机及管道应安装稳固,氧气管、燃气管与机体连接正确,连接处不得漏气。
4.3.2管道切割机的轨道安装应符合下列规定:
1轨道式管道切割机的轨道安装前应对安装表面进行检查。安装表面应平整光滑无异物,焊缝余高应磨平。
2吸附式轨道的磁铁安装前应检查吸附力,使用前应检查磁铁与管壁的接触状态。
3卡箍式轨道还应符合以下要求:
1)选用的轨道或轨道组应与被切割管道直径相适应。
2)每根轨道应配一个爪具。爪具的孔端与轨道的螺柱端应配合紧固。
3)安装完成后应逐一检查爪具钩端与轨道拉紧孔的扣合以及轨道与管壁的贴合情况。
4.3.3数控切割机安装应符合下列规定:
1割炬应装在小车有护板的一侧,与护板保持不小于100m的距离。气管连接到分配器之前,应清除气管内杂物。
2动力源应带有交流稳压装置。机床、小车、轨道等设备应有可靠的接零接地。
3操作平台的安全护栏、上下平台的扶手、踏步应符合安全要求。切割机周围设置的安全通道和作业空间不应小于600 mm。
资源链接 请先登录(扫码可直接登录、免注册)点此一键登录 ①本文档内容版权归属内容提供方。如果您对本资料有版权申诉,请及时联系我方进行处理(联系方式详见页脚)。
②由于网络或浏览器兼容性等问题导致下载失败,请加客服微信处理(详见下载弹窗提示),感谢理解。
③本资料由其他用户上传,本站不保证质量、数量等令人满意,若存在资料虚假不完整,请及时联系客服投诉处理。
DL/T 5832-2021 水电水利工程施工机械安全操作规程 自动埋弧焊机
ICS27.140
CCS P59 DL
中华人民共和国电力行业标准
DL/T5832-2021
水电水利工程 施工机械安全操作规程 自动埋弧焊机
Safety operation code for construction equipment of hydropower and water conservancy engineering
Automatic submerged arc welding machine
2021-04-26发布2021-10-26实施
国家能源局发布
1总则
1.0.1为规范水电水利工程自动埋弧焊机的安全操作,制定本规程。
1.0.2本规程适用于水电水利工程金属结构制造安装工程,不适用于有压或残留有易燃、易爆、有毒、有害物质的容器、管道的自动埋弧焊的焊接施工。
1.0.3自动埋弧焊机的安全操作除应遵守本规程外,尚应符合国家现行有关标准的规定。
2术语
2.0.1埋弧焊机submerged arc welding machine
电弧在颗粒状焊剂层下燃烧以进行焊接的弧焊机。
2.0.2焊车welding automobile
装有焊接机头、送丝机构、控制盘等的电动小车,与弧焊电源等配套,可组成自动焊设备。
2.0.3小车welding tractor
自动埋弧焊机中承载特定对象且能够由电动机驱动行走的机构。
2.0.4焊接大车welding car
筒体横焊机中由电动机驱动的装有焊接电源、机头、控制箱、焊剂托盘、行走机构,可沿焊件上端或专门支架行走的部分。
2.0.5焊接供电电缆welding supply cable
焊接电源与焊炬或焊枪或电焊钳之间的电缆。
2.0.6焊接返回电缆welding return cable
焊接电源与工件之间的连接电缆。
2.0.7导电嘴contact tube
熔化极(电)弧焊机的焊枪或焊接机头上用以将焊丝导向熔池并向焊丝馈送电流的零件。
2.0.8焊接机头welding head
自动埋弧焊机中,用以将焊丝导至焊接区,并馈送焊接电流的装置。
2.0.9焊接操作机manipulator
将焊接机头或焊枪送到并保持在待焊位置,或以选定的焊接速度沿规定的轨迹移动焊接的装置。
2.0.10筒体横焊机barrel ring welding machine
能完成大型(直径大于4m)立式筒体环缝焊接的通用自动埋弧焊接设备。
2.0.11焊剂托盘fluxtray
用于自动埋弧焊平焊位打底焊时在焊口背部,或横焊位焊接时在焊口下沿支托焊剂的装置。
3基本规定
3.0.1设备使用单位应建立安全制度及规程,并保持其有效。作业人员应掌握并遵守安全制度及规程,按焊接工艺规程操作。
3.0.2从事焊接设备操作、吊装与维护的人员,应经过安全和专业技能培训及考核,熟知本规程,持证上岗。
3.0.3露天安装的焊机应在高于地面的通风干燥处,应设防雨、防砸设施。
3.0.4焊接应在通风良好、无火灾隐患的场所实施。雷雨天不得露天作业。
3.0.5焊接区域应明确标识和警示。焊接部位下方不得有人员通行或逗留。
3.0.6自动埋弧焊不宜在封闭空间内施焊。确有需要时,应采取相应的通风、防触电等安全保护措施。
3.0.7自动埋弧焊机宜与起重机、卷板机、立式车床等频繁启停的大功率设备分开供电。
3.0.8自动埋弧焊机的操作,除遵守本规程外,还应符合《焊接与切割安全》GB9448、《水电水利工程施工通用安全技术规程》DLT5370、《水电水利工程金属结构与机电设备安装安全技术规程》DLT5372、《水电水利工程施工作业人员安全操作规程》DL/T5373的规定。
4安装与调试
4.1安装
4.1.1设备安装应遵守设备安装使用说明书。电气设备及元器件按《建设工程施工现场供用电安全规范》GB50194的要求安装。焊接电源应按《弧焊设备第1部分:焊接电源》GBT15579.1的要求安装。
4.1.2购入或转入设备的技术文件应齐全。对转入的旧设备,安全性不能确定时,在投入使用前应由设备部门组织鉴定。鉴定过程和鉴定结论应记录存档。鉴定人员至少应包含电气、焊接、安全、结构等相关的专业人员。
4.1.3焊机应使用工业用熔断器。熔断器应由专业电工安装与更换,不得用其他金属丝替代熔断器的熔丝。
4.1.4焊接电源宜安装在固定的支架(平台)上,宜采用快速接头,连接牢靠,接触良好。焊接电源距焊点不宜大于30,焊接电缆长度不宜大于50m。焊机的接线桩、极板和接线端应装防护罩。
4.1.5焊接电缆的强度、绝缘性能、导电性能和密封性能应满足焊接安全要求。
4.1.6按“一机一闸一漏”设置漏电保护器。漏电保护器的安装与测试应由专业电工及测试人员操作。
4.1.7非移动结构的龙门式埋弧焊机宜安装在混凝土基础上。可移动龙门式埋弧焊机应安装卡轨器、止动器。
4.1.8只有焊接操作机立柱的基础混凝土强度、地脚螺栓的紧固力满足受力要求后,才可进行横臂的吊装。4.1.9筒体横焊机的安装还应遵守以下规定:
1焊接大车吊装前,将焊接大车内的焊接电源、机头、控制箱(表盘)、焊剂托盘等系统或机构在地面安装完成,且固定可靠。
2焊接电源、机头、控制箱的防护棚宜在地面组装。
3焊接大车上不得堆放杂物,非工作人员未经许可不得上车。
4检查并清除焊接大车行车线路上的障碍物。
4.1.10对于大型辅助设备如空气压缩机、变位机、滚轮支架、滚焊移动平台等的安装,应编制安装措施。现场制造的非标工作平台,其结构应满足安全要求,设计、审核、批准程序应完整。
4.1.11功能不同的电缆应标记明显。
4.1.12拆装焊车前应关闭焊接电源或切断输入电源。
4.2调试
4.2.1安装工作完成应由焊工、电工及时对设备进行检查、调试。
4.2.2调试前应对紧固件、调节装置、行走机构进行复查。
4.2.3启动电动机前,校对接线,确定接线正确方可点动电动机。当电动机转动方向与所需方向一致时,方可进行下一步工作。
4.2.4安装齿链或齿轮等传动机构时,不得随意转动机械。需要转动检查齿轮啮合情况时,不得戴手套操作与检查,长发应戴头套。
4.2.5空载试验:将焊接电源置于埋弧焊挡位,焊剂回收装置正常。按“启、焊、停”的程序在空载状态下连续操作3次,控制系统应无异常。
4.2.6焊接试验:按焊接工艺规程中的大、中、小电流及相应电压、焊速分别进行“启、焊、停”的操作。电流、电压、焊速的调整应缓慢进行,无异常情况发生。
资源链接 请先登录(扫码可直接登录、免注册)点此一键登录 ①本文档内容版权归属内容提供方。如果您对本资料有版权申诉,请及时联系我方进行处理(联系方式详见页脚)。
②由于网络或浏览器兼容性等问题导致下载失败,请加客服微信处理(详见下载弹窗提示),感谢理解。
③本资料由其他用户上传,本站不保证质量、数量等令人满意,若存在资料虚假不完整,请及时联系客服投诉处理。
答疑:求17J925-1图集,305906532!谢谢!!-安徽
问题专业: 土建 施工 结算 钢结构算量GJG
所属地区: 安徽
提问日期: 2022-08-02 14:54:12
提问网友: 刘明慧
解答网友: 钢筋撑起半边天
接收
答疑:在结构图中识别楼层表,识别完成就变成建筑标高了,画梁板变成建筑标高-安徽
问题专业: 土建计量GTJ
所属地区: 安徽
提问日期: 2022-08-02 14:53:59
提问网友: 叶正忠
就是绘制梁板以后发现,梁板的标高是建筑标高了,首层层高3.9,第二层2.9,结构应该是2.82啊
解答网友: 小野猫
这没有多少影响的,总高度对就行
问题专业: 土建 概算 土建计量GTJ
所属地区: 山东
提问日期: 2022-08-02 14:52:50
提问网友: 杜兆龙
解答网友: 红梅傲雪
这样的条基怎么画啊,下面的c15素砼是垫层还是条基
——:混凝土垫层
上面的紫色的是什么怎么画
——:砖基础,
混凝土基础三个单元,底单元,600*300的混凝土基础,第二个单元:370*120的砖基础,第三个单元240*830的砖基础
再布置基础圈梁
DL/T 5831-2021 水电水利工程竖井压力钢管吊装施工导则
ICS27.140
CCS P 59 DL
中华人民共和国电力行业标准
DL/T5831-2021
水电水利工程 竖井压力钢管 吊装施工导则
Guide for lifting technology of shaft steel penstock in hydroelectric and hydraulic engineering
2021-04-26发布2021-10-26实施
国家能源局发布
1总则
1.0.1为规范水电水利工程竖井压力钢管吊装施工,合理选择施工设备和安装方法,制定本导则。
1.0.2本导则规定了水电水利工程压力钢管竖井吊装的施工方法及技术要求。
1.0.3本导则适用于水电水利工程竖井压力钢管吊装施工。
1.0.4水电水利工程竖井压力钢管吊装施工,除应符合本导则外,尚应符合国家现行有关标准的规定。
2术语
2.0.1吊装单元install unit
单个或由多个管节组焊成的一个运输吊装整体。
2.0.2载人吊装系统manned hoisting system
用于人员上下竖井运输装置的统称。一般由吊装设备、牵引设备、载人吊笼等组成。
2.0.3操作平台系统operation platform system
用于施工人员进行钢管安装的装置,一般由吊装设备、牵引设备、操作平台等组成。
3基本规定
3.0.1施工应制定专项方案并经过评审。
3.0.2竖井开挖支护验收合格,完成钢管通过性试验。
3.0.3吊装系统应进行负荷试验,系统应整体验收。
3.0.4待安装的吊装单元已验收合格。其他要求符合《水电水利工程压力钢管制作安装及验收规范》GB50766的规定。
3.0.5作业人员应接受安全技术交底和培训,并持证上岗。
3.0.6测量放样应按设计文件执行,测量仪器应按规定检定合格。施工测量应符合《水电水利工程施工测量规范》DLT5173的规定。
3.0.7施工现场应配备通风设施,设施布置合理,通风排烟时应控制风速和风量。
3.0.8竖井粉尘、有毒物质在空气中的允许浓度及限值应符合《水电水利工程施工通用安全技术规程》DL/T5370的规定。
3.0.9施工场所应设置满足需要的照明设施。钢管卸车翻身及上下弯管段等特殊施工面应适当增加照明,人员安全通道应设置应急照明。施工照明用电应符合《水电水利工程施工通用安全技术规程》DLT5370的规定。
3.0.10施工现场通信应可靠畅通,宜设置备用通信方式。
3.0.11吊装单元在竖井内吊装的全过程宜进行视频监控,在上下弯段宜加强监控,摄像头应具有夜视功能,监控系统数据保留不宜少于15天。
4设备与设施
4.1起重设备
4.1.1露天或洞内直径较大的钢管吊装起重设备宜采用门式起重机、桥式起重机。
4.1.2较小直径的钢管吊装可采用固定提升吊装系统,并应设置限位装置。
4.1.3露天且钢管长度较短的钢管吊装可采用汽车起重机。
4.1.4吊装设备应采用双制动,并充分考虑冲击载荷的影响。
4.1.5起重设备的额定载荷取值应考虑最不利的载荷总和。
4.1.6起重设备安装及验收应按《起重设备安装工程施工及验收规范》GB50278执行。
4.1.7起重设备的布置应遵循减少洞室扩挖,便于安装、拆除和运输的原则,位置、高度应满足钢管卸车、翻身、吊装空间尺寸要求。
4.1.8起重设备基础应经专项设计。
4.2人员通道
4.2.1竖井井口周边应设置人员通道,且不得影响钢管的正常安装,与吊装设备运行空间不宜小于200mm。
4.2.2人员通道的走道板、楼梯、扶手、踢脚板、搭设的临时脚手架、安全警示标识等应符合《水电水利工程施工通用安全技术规程》DLT5370的规定。
4.3载人设施
4.3.1载人设施应单独布置,并不得影响钢管运输、吊装。
4.3.2载人设施宜布置在地质条件良好的位置,并加强防护。
4.3.3载人设施应有导向装置,制动系统具备双保险功能。
4.3.4载人设备钢丝绳的安全系数不应小于14。
4.3.5载人设备和吊笼应进行载荷试验,并经验收合格后方可使用。
4.3.6载人设备的安全防护设施应符合《水电水利工程施工安全防护设施技术规范》DL/T5162的规定。
4.4操作平台
4.4.1压缝台车、焊接台车、检验台车等操作平台可设计为一体,采用多层结构,车轮与管壁接触面应为非金属材料。
4.4.2操作平台系统安装完成后应进行验收。
4.4.3操作平台上应设锁定装置。非运行状态时,应将操作平台锁定在已安装好的钢管上,平台上的设备应固定牢靠。
资源链接 请先登录(扫码可直接登录、免注册)点此一键登录 ①本文档内容版权归属内容提供方。如果您对本资料有版权申诉,请及时联系我方进行处理(联系方式详见页脚)。
②由于网络或浏览器兼容性等问题导致下载失败,请加客服微信处理(详见下载弹窗提示),感谢理解。
③本资料由其他用户上传,本站不保证质量、数量等令人满意,若存在资料虚假不完整,请及时联系客服投诉处理。
问题专业: 公路
所属地区: 安徽
提问日期: 2022-08-02 14:48:47
提问网友: DDM
解答网友: 泡8喝9
就是路边标线,振荡表示用振荡漆套定额。W应该是万的意思,指几万平方的漆面。
问题专业: 机电 安装算量GQI
所属地区: 北京
提问日期: 2022-08-02 14:48:01
提问网友: 蒋欣
解答网友: WWWei
就近的220V强电电源
DL/T 2217-2021 变压器用天然酯和合成酯油溶解气体分析导则
ICs29.040.99
CCS E 38
中华人民共和国电力行业标准
DL/T2217一2021
变压器用天然酯 和合成酯油溶解气体 分析导则
Guide for interpretation of gases generated in natural ester and synthetic ester-immersed transformers
2021-01-07发布2021-07-01实施
国家能源局发布
1范围
本文件规定了变压器用天然酯和合成酯油溶解气体的分价方法。
本文件适用于以天然酯绝缘油或者合成酯绝缘油为主要绝缘材科的电力变压器。
2规范性引用文件
下列文件中的内容的规范性引用而构成本文件必不可少的条款。其中,注日期的引用文件,仅该日期对应的版本适用本文件:不注日期的引用文件,其最新版本(色括所有的修改单)适用于本文件。
GB/T7597电力变压器油、汽轮机油)取样方法
GBT17623-291渔缘油中溶解气体组分含量的气相色谱测定法
GB50150电安装工程电气设备交接试验标准
NB/SH/T 0930力下绝缘液体产气特性测定法
ASTM D7150测定热应力下绝缘液体放气特性的标准试验方法(Standard test method for the deter mination of gassing haracteristics of insulating liquids under thermal stress)
3术语和定义
下列术语和定义适用月于本文件。
3.1
特征气体characteristic gas
对判断充油电气设份沙部故障有价值的气体,即氢气(H,D、甲烷(CH4)、乙烷(CH)、乙烯(CH)、乙炔(C2H2)、化碳(C0)、二氧化碳(C02)。
[来源:DL/T722-20141门
3.2
天然酯绝缘油natural ester insulating oil(hereinafter referred to as matural ester)
从种子或其他生物材料中提取,用于变压器或类似电气设备的鲍缘液体,其主要成分是甘油三酯,具有良好的生物降解性和环境相容性,简称天然酯。
[来源:DLT1811一2018,3.1,有修改]
3.3
合成酯绝缘油synthetic ester insulating oil(hereinafter referred to as synthetic ester)
有机酸与醇(如季戊四醇)经过酯化反应得到的绝缘油,简称合成酯。
3.4
高油酸基天然酯绝缘油higholeic based natural ester insulating oil
油酸含量大于75%的天然酯绝缘油。
3.5
高油酸基葵花型天然酯绝缘油higholeic sunflower based natural ester insulating oil
具有典型脂肪酸组成(油酸82%,亚油酸9%,亚麻酸小于1%)的高油酸基天然酯绝缘油。
3.6
大豆基天然酯绝缘油soybean-based natural ester insulating oil
从大豆中提取的具有典型脂防酸组成(油酸24%,亚油酸54%,亚麻酸7%)的天然酯绝缘油。
3.7
菜籽基天然酯铯缘油rapeseed-based natural ester insulating oil
从菜籽中提取的具有典型脂防酸组成(油酸62%,亚泊酸22%,亚麻酸10%)的天然酯绝缘油。
3.8
总溶解性可燃气体total dissolved combustible gas
氢气、甲烷、乙烷、乙烯、乙炔和一氧化碳气体含量的总和。
3.9
杂散产气stray gassing
设备正常运行或未发生故障的过载运行条件下,酯类绝缘油所产生的气体。
3.10
酯类绝缘袖变压器ester insulating oil transformer
内充天然酯绝缘油或合成酯绝缘油作为绝缘介质的变压器。
3.11
典型值typical value
酯类变压器在正常运行状态下油中特征气体的具有代表性的浓度值。
4油中气体的来源
4.1酯类绝缘油与矿物绝缘油产气差异
天然酯和合成酯绝缘油(以下简移“酯类绝缘油”)含有丰富的酯基和C16一C18链,矿物绝缘油主要为烷烃、环烷烃和芳香烃等,化学结构的差异性导致两者在故障状态下产生的气体种类虽然相同,但比率和产气率有较大差异。酯类绝缘油与矿物绝缘油产气最显著的差别如下:
a)非故障条件下,含有亚麻酸的酯类绝缘袖会产生乙烷;
b)过热产生的甲烷、乙烷和乙烯含量更高,且相比矿物绝缘油在更低温度下产生;
c)过热产生的甲烷、乙烷和乙烯的比例和矿物绝缘油不同;
d)酯类绝缘油过热产生大量的二氧化碳和一氧化碳。
4.2杂散产气
杂散产气是指设备正常运行或未发生故障的过载运行条件下,天然酯(合成酯)绝缘油所产生的气体。杂散气体的检测参照NB/SH/T0930或ASTM D7150。由于亚麻酸氧化时会产生乙烷,选用亚麻酸含量较高的大豆基或菜籽基天然酯类绝缘油作为绝缘介质的电气设备,即使在正常运行和未发生故障的过载运行条件下,也会产生杂散气体乙烷,浓度可以达到几百微升每升。但随着时间的推移,乙烷浓度趋于稳定,应对杂散产气进行监测直至气体稳定并建立趋势基线。
4.3酯类绝缘油在电应力作用下的产气
4.3.1概述
在相同条件下,合成酯绝缘油中放电产生的故障气体含量与矿物绝缘油相近,而天然酯绝缘油中放电故障产生的气体含量比矿物绝缘油低一个数量级。附录A中的大卫三角形法说明,在PD区(局部放电)和D1区(低能放电),天然酯(合成酯)绝缘袖和矿物绝缘油产生的特征气体比值相近。
4.3.2局部放电
酯类绝缘油变压器局部放电产生的特征气体主要是氢气(H2)和甲烷(CH4)。
4.3.3电弧放电
酯类绝缘油变压器电弧放电产生的特征气体主要是氢气(H)、乙炔(CH)、乙烯(CH4)。酯类绝缘油和矿物绝缘油生成的氢气和碳氢化合物比例相近,但二著的产气率有所差异,生成的碳氧化合物比例也不同。
4.4酯类绝缘油在热应力作用下的产气
4.4.1概述
当达到一定的过热温度,酯类绝缘油通过碳氢链热分解、酯键热分解、游离酸组分反应及杂散产气等生成气体,其产气总量为矿物绝缘油的两倍以上,试验数据见附录B和附录C。
4.4.2酸性产物
甘油三酯的分解是天然酯(合成酯)绝缘油热解的主要反应之一。它将生成两种游离脂肪酸、丙烯醛和来自第三种脂肪酸的乙烯酮。该反应虽未生成气体产物,但是每种产物可进一步反应产生碳氧化合物、乙烯、甲烷和乙烷。总酸值随着反应的发生而上升,说明碳氧化合物、乙烯、甲烷和乙烷均由酯类绝缘油的热解产生。
4.4.3碳氧化合物
酯类绝缘油热解产生的碳氧化合物为一氧化碳和二氧化碳,碳氧化合物的含量与酸值均随着热解温度的升高而增长,在相同温度下矿物绝缘油所产生的碳氧化合物比酯类绝缘油小几个数量级。此外,酯类绝缘油所产生的碳氧化合物含量也可能远大于纤维素绝缘纸,这将对纤维素绝缘纸老化程度的判断造成干扰,可通过酸值及乙烯含量来辅助判断气体来源。
4.4.4乙烯
酯类绝缘袖热解产生乙烯的温度较矿物绝缘油低50℃一100℃,且在较高温度范围内仍然显著增加。通常情况下,天然酯类绝缘泊中乙烯的含量不会超过一氧化碳的含量,但在一定高温下含量却明显超过一氧化碳含量,这种情况与矿物绝缘油相似。
4.4.5甲烷和乙烷
酯类绝缘油热解过程中烃链断裂产生甲烷和乙烷,甲烷和乙烷的热解温度均较矿物绝缘油低50℃一100℃,酯类绝缘油中甲烷和乙烷的产气特性与矿物绝缘油更为相似。在高温条件下,酯类绝缘油热解产生的甲烷和乙烷含量相近,但在矿物绝缘油中并非如此。造成油中甲烷和乙烷产物含量和比例差异的根本原因是天然酯绝缘油和矿物绝缘油具有不同的烃结构。
4.4.6可燃性气体
酯类绝缘油在高温下会产生可燃性气体。气体的含量和产气率取决于酯类绝缘油类型、暴露于高温下的含量和曝光时间等,可燃性气体比率的变化反映了设备故障的严重程度,必要时应采取额外指施。
资源链接 请先登录(扫码可直接登录、免注册)点此一键登录 ①本文档内容版权归属内容提供方。如果您对本资料有版权申诉,请及时联系我方进行处理(联系方式详见页脚)。
②由于网络或浏览器兼容性等问题导致下载失败,请加客服微信处理(详见下载弹窗提示),感谢理解。
③本资料由其他用户上传,本站不保证质量、数量等令人满意,若存在资料虚假不完整,请及时联系客服投诉处理。
DL/T 2216-2021 火力发电厂废水处理系统检修导则
ICS27.100
CCS F 29 DL
中华人民共和国电力行业标准
DL/T2216-2021
火力发电厂 废水处理系统 检修导则
Guide for maintenance of wastewater treatment system in thermal power plant
2021-01-07发布2021-07-01实施
国家能源局发布
1范围
本文件规定了火力发电厂废水处理系统检修的基本原则,检修计划、检修周期,检修开工前准备,检修项目及质量要求,检修旅工、安全质量管理,试运存,检修评价及总结等相关内容。
本文件适用于火力发电厂度水处理系统检修。
2规范性引用文件
下列文件中的内文中的规范性引用而构成本文件必不可少的条或。其中,注日期的引用文件,仅该日期对应的版根适用于本文件:不注日期的引用文件,其最新版本(包挂所有的修改单)适用于本文件。
GB/T11651体防护装备选用规范
GB/T12801生产过程安全卫生要求总则
GB/T19001质局管理体系要求
GB26164.1电业安全工作规程第1部分:热力和机根
GB26860电喷全工作规程发电厂和变电站电气部分
DL/T 838力发电企业设备检修导则
DL/T1123线电企业生产安全设施配置
3术语和定义
下列术语和定义透手本文件。
3.1
定期检修time based maintenance
一种以时间为基础的预性检修针对废水处理系统设备的特点,事先确定检修间隔、检修项目、需用备件及材料等检修方式。
3.2
状态检修condition-based maintenance
根据状态监测和诊断技术提供的设备状态信总评估没备的状况,在故障发生前进行检修的方式。
3.3
质检点(H点、W点、S点)quality control points(hold point,.witness point,,standby point)
在检修工序管理中,根据某道工序的重要性和难易程度设置的关键工序质量控制点,这些控制点不经质量检查签证不得转入下道工序。其中H点(hold point)为停工待检点,W点(witness point)为见证点,S点(standby point)为旁站点。
3.4
检修间隔maintenance interval
从检修后设备系统投运开始至下一次检修停运的时间。
4检修基本原则
4.1废水处理系统检修应纳人火电厂全厂检修计划,规范检修管理,提高检修质量,实现废水处理系统安全、环保、经济、可靠运行。
4.2废水处理系统检修应按照GB/T11651、GB/T12801、GB26164.1、GB26860、DL/T1123等规定,制定防火、防室总、防中毒、防触电、防溺水、防危化品伤害等预防控制措施,科学安排作业工序,应严格执行检修作业指导书,杜绝各类违章,确保人身和设备安全。
4.3脱硫系统检修管理应贯彻执行GB/T19001等质量管理体系,环境管理体系要求,推行全过程质量管理和标准化作业。
4.4废水处理系统检修应在做好定期计划检修的基础上,通过设备状态诊断技术分析,逐步扩大状态检修的比例。
4.5检修有关人员应然知系统和设备的构造、性能和原理,罩握设备的检修工艺、质量标准
4.6废水处理系统主要包含化学废水、脱硫废水、含煤废水、含油废水、灰渣水处理系统等。
4.7废水系统的电动门、消防水系统、一般构筑物、电气系统、控制系统等常规设备和系统的检修,可参照DL/T838等相关标准执行。
资源链接 请先登录(扫码可直接登录、免注册)点此一键登录 ①本文档内容版权归属内容提供方。如果您对本资料有版权申诉,请及时联系我方进行处理(联系方式详见页脚)。
②由于网络或浏览器兼容性等问题导致下载失败,请加客服微信处理(详见下载弹窗提示),感谢理解。
③本资料由其他用户上传,本站不保证质量、数量等令人满意,若存在资料虚假不完整,请及时联系客服投诉处理。
DL/T 2207-2021 电力电容器噪声测量方法
ICs31.060.70
CCS K 42 DL
中华人民共和国电力行业标准
DL/T2207一2021
电力电容器 噪声测量方法
Noise measurement of power capacitors
2021-01-07发布2021-07-01实施
国家能源局发布
1范围
本文件规定了电力电容器单元的声压级测量方法,并以此来确定电力电容器单元的声功率级。
本文件适用于标称电压1kV及以上、频事为0Hz的电力系统用进联电容器单元、交流滤波电容器单元、直流滤波电容器单元其他电电容器单元可参考本作执行。
本文件不适用于本体高分8m的电容器。
2规范性引用文件
下列文件中的内通文中的规范性引用而构成文件必不可少的条款其中,注日期的引用文件,仅该日期对应的造用于本文件:不注日期的引用文作,其最新版本《包括所有的修政单)适用于本文件。
GBT2900.16色术语电力电容器
GB/T3241倍频程和分数倍频程滤波器
GB/T3767-声学声压法测定噪声源声功率级和声能量级反射面上才近似自由场的工程法
GBT3785.1学声级计第1部分:规范
GB/T 3947声学名词术语
3术语和定义
GB/T2900.16、G00767一2016和GBT3947界定的以及下列术语和定义适用手本文件。
3.1
噪声noise
断续或统计上随机的不要的声音。
注:在本文件中专指人可铜范围。
3.2
声压sound pressure
有声波时,媒质中的压力与静压的差值。
注:声压单位为帕(Pa》。
3.3
声压级sound pressure level
4燥声测
4.1测量条件
4.1.1并联电容器电源注入要求
并联电容器最大允许注入电流约定为:基波电流不大于11(为电容器额定电流)。谐波电流按直流换流站中并联电容器的噪声计算谐波电流中的各次谐波进行选取,基波与谐波电流的合成电流不大于1.30。
4.1.2交流滤波电容器电源注入要求
交流滤波电容器的注入电流按基波电流叠加谐被电流进行加载,谐波电流按直流换流站中滤波器的噪声计算诺波电流中的主谐波或各次谱波选取。
4.1.3直流滤波电容器电源注入要求
施加的谐被电流按直流换流站中直流滤波器的噪声计算谐波电流中的各次谐波进行选取,同时施加电容器单元最大持续直流运行电压。
4.2测量环境
电力电容器单元的噪声测量应在消声室或背景噪声不大于30B(A)、测量时实验室内不会产生影响测量结果的声波折反射的环境中透行。测量前后,应在试验电源启动且空载条件下测量每个测点的背景噪声。背景A计权声压级应较电力电容器单元在规定试验条件下测量的A计权声压级小10B(A),当不能满足此规定时,至少应满足4.6.2的规定。
4.3基本测量设备
测量声压级时,应使用符合GB/T3785.1的1级声级计,并按照GB/T3767一2016的规定进行校准。倍频程或13倍频程滤波器应符合GB/T3241的要求。
4.4试品布置
进行电力电容器噪声测量时,应采用基本不影响电容器噪声的产生和传播的固定方式,一般按电容器实际安装姿态,采用安装架结构固定,试品距地面距离不应小于0.8m。
4.5传声器布置
电力电容器基准发射面构成的长方体(包括套管)各面分别沿各自法线方向向外平移0.3m,这样就构成了一个更大的长方体,该长方体各面围成的表而即为测量表面,传声器的数量和位置取决于电容器的尺寸和测量距离。附录A提出了确定传声器数量和位置的方法。如果以下至少有一种情况出现,则应使用附加传声器位置做进一步测量:
a)测量的A计权声压级的变化范围(即最高声压级和最低声压级的分贝差)超过测量点的数目;
b)被测噪声源发射噪声的A计权表观指向性指数在任意方向上超过5B;
c)附加传声器位置按GBT3767一2016附录C的方法布置。
传声器应位于测量而上,彼此间距大致相等,对于只设置1个测点的而,应将测点设置在该面的中点上。测量时,应将传声器垂直于基准发射面的方向布置。
4.6声压级测量
4.6.1测量要求
测量应在背景噪声值近似恒定时进行,在即将对试品进行声压级测量前,应先测出背景噪声的A计权声压级。测量背景噪声时,传声器所处的位置应与测量试品噪声时其所处的位置相同。当测点总数超过10个时,允许只在试品周围星均匀分布的10个测量点上测量背景噪声。对于每一测点上的A计权声压级都应予以记录,应使用仪器的快速响应指示,以便确认和避免由于暂态背景噪声而引起的测量误差。测量完毕且切除试品后,应立即重复测量背景噪声。每次测量前、后,应用传声器准确度不低于±0.3dB(按GB/T3785.1规定的1级要求进行)的声校准器校准,如果二次校准变化超过03B,则本次测量结果无效,应重新进行测量。