FIRESUPPRESSIONSYSTEMS FM-200TOTALFLO0D
DESIGN INSTALLATION AND MAINTENANCE MANUAL
Authorized ANSULe FM-200TM and SAPPHIREe Engineered System Distributors
FROM: Product Management - Engineered Systems
SUBJECT: New Electric Actuator for ANSUL: SAPPHIRE and FM-200 Systems
Johnson Controls is pleased to introduce the UL Listed FM Approved and LPCB Redbook Listed Electric Actuator(Part No. 304205030) for both SAPPHIRE and FM-200 Fire Suppression Systems. The new design of the electric
FIGURE1ELECTRIC ACTUATOR (Part No. 304205030) 010684
the permanent magnet and allows the spring to push and latch the actuator pin into the fire position. The service lifeof the electric actuator has been extended to 25 years.
This bulletin serves as an addition to the following UL/FM approved manuals and wilbe added to the manuals at the next update.
October 9 2015 ANSULe SAPPHIRE System Design Installation and Maintenance Manual (Part No. 57059O) datedSeptember 1 2010 ANSUL? SAPPHIRE System Design Installation and Maintenance Manual (India Version --Part No. 570805) dated September 2015
One Stanton Street Marinette WI 541432542
Bulletin No. 2018265May 13 2019 Page 2
Third party approvals cover the following system operating conditions:
25 Bar FM-200 32°F to 130 °F(0 °℃ to 54 °℃)25 Bar SAPPHIRE32°F to 130°F(0°℃ to 54 °℃)
Electric ActuatorTechnical Specifications are asfollows:
Body Finish Electroless Nickel Plate Mild SteelActuator Pin Stainless SteelConnection 1 in.BSPPElectrical Connection 1/2 in. NPT (F) conduit connection
These installation instructions are intended for use with the Electric Actuator (Part No. 304205030). Personnelbefore attempting to install or service any electric actuator.
Bulletin No. 2018265May 13 2019 Page 3
AWARNING
The fire suppression system could actuate introducing a potentially hazardous environment causing instructions and follow them carefully during installation.
INSTALLATION
panel which has been qualified for releasing device service. The UL Listed fire alarm control panel shallhave been Installation of the electric actuator shall be to the supervised releasing device circuit of a UL Listed fire alarm controlUL Listed fire alarm control panel manual for information on allowable device patibility. found patible for use with the electrical actuator (Part No. 304205030) covered in this Bulletin. Reference the
Install the electric actuator to the top of the valve assembly as follows:
1. Ensure the electric actuator pin is in the non-fired position by fully screwing in the reset tool0.27 in. (6.85 mm).2. Remove the dust cap from the top of the discharge valve assembly.3. Carefully thread the electric actuator onto the discharge valve between the valve and manualactuator until handl-tight.
ud o p iu) n s ud nsu pue ( a pn)n
ACAUTION
container to actuate.
actuator.
4. Wiring the actuator to the releasing circuit of the UL Listed Fire Alarm Control Panel:30 mA. The conduit connection on the electric actuator is 1/2 in. NPT (F)
For the release circuit
a. Using threaded conduit connection on the electric actuator pulleads through to a junction box to makeb.Connect Positive from the release circuit to either the black or white lead wire. connections.Note: Actuator contains bridge rectifier therefore polarity can be reversed.c.Connect Negative from the release circuit to the opposite lead from step 2.d.Installthe in-line supervisory device into the circuit if required. (Refer to control panel instructions.)
For the placement indicator circuit (supervised)
a.Using threaded conduit connection on the electric actuator pulleads through to a junction box to makeconnections.b.Connect Positive from the input circuit to either one of the yellow or orange pairs.c.Connect Negative from the input to the opposite lead from step b. d. Of the remaining yellow and orange wire place the End-of-Line resistor (EOL). (Refer to control panelinstructions for appropriate value.
Marinette WI 541432542 One Stanton Street