STANDARD FOR
ACCEPTANCE TESTING SPECIFICATIONS
FORELECTRICALPOWEREQUIPMENT&SYSTEMS
2017 NETA STANDARDS
AMERICANNATIONALSTANDARD
STANDARDFOR ACCEPTANCETESTINGSPECIFICATIONSfor ElectricalPowerEquipment and Systems
Secretariat
InterNationalElectricalTestingAssociation
American NationalStandardsInstitute
This page intentionally left blank
Erratato ANSI/NETAATS-2017 StandardforAcceptanceTestingSpecificationsfor ElectricalPowerEquipmentandSystems
Issued by the
NETA Standards Review Council
Of the
InterNational Electrical TestingAssociation
Correction sheet
Issued May 21 2017
Printed in the United States of America.
This correction sheet may be freely reproduced and distributed in order to maintain the utity and currencyof the underlying Standard. This correction sheet may not be sold licensed or otherwise distributed for anymercial purposes whatsoever. The content of this correction sheet may not be modified.
21 May 2017
7.2.2 Transformers Liquid-Filled
7.2.2.B.7
edo se () p aq pinous sis sisfiue asudsn ouanban deams oa Original text incorrectly had the SFRA test as mandatory.
7.2.2 Transformers Liquid-Filled
7.2.2.D.5
Original text is incorrectly shown as 150%.
Cables Medium-and High-Voltage
7.3.3.B.4
TDR measurements should be marked (*) as optional.Original text incorrectly had the TDR test asmandatory.
Circuit Breakers Vacuum Medium-Voltage
7.6.3.B.5 (electrical test)
7.6.3.D.5 (test result)
Dynamic contact resistance test.Delete requirement and expected test results section this test was not intended for medium- voltage vacuum breakers.