NOTIFIER

PN 54014:B2 04/25/2014 14-0370

1ProductOverview

The High-Speed Network Communications Module (HS-NCM) provides a means for connecting specific Notifier firealarm control products to High-Speed NOTIFIRENETTM There are six types of HS-NCMs available: HS-NCM-W for connecting nodes with twisted-pair wire; HS-NCM-MF and HS-NCM-SF are used for connecting nodes with fiber-opticcable; HS-NCM-WMF and HS-NCM-WSF are used for connecting nodes with fiber-optic cables to nodes with twisted-pair wire; HS-NCM-MFSF for connecting nodes with multi-mode fiber cable to nodes with single-mode fiber cable. The following equipment may be used with the HS-NCM:

UL 8th Edition**

UL 9th Edition*

NFS2-3030 NFS2-640NFS-320NCA-2 DVC-EMONYXWorks

NFS-3030 NFS-640NCA

Pf HSNCMfseithUL 9hEdins svidd vi NUP ti FACPifrn xlULC Istd pl. * - Power for the HS-NCM for use vit UL Sh Edition pmels must be prided by a 24 VDC UL/ULC lisod power spply.

The following revisions of the UL 9th edition panels require a 24 VDC UL/ULC listed power source to power the HS-NCM and can not be powered via the panel's NUP port:

NFS-320 NFS2-640 CPU2-640PCB Revision E or older CPU2-640PCB Revision E or olderNFS2-3030 CPU2-3030PCC Revision I or olderDVC-EM DVC DVC-PCA-All Revisions DVC-EMPCB Revision F or olderNCA-2 NCA-2PCC Revision I or older

NUP Po The revisice Its are sill eqguired for usisatio between the HS-NCM and the fire panel rand on h fire panl’s cirit d.

NOTE: All wiring connections are supervised and power limited.

One HS-NCM can provide network munication for up to two nodes (including fire alam control panels and networkannunciators).

Per UL 864 9th Edition the HS-NCM uses Active Multiplex Type 3 Communication.

limits between two nodes.Forconfiguration and setup information refer to “HS-NCM Configuration on page 5.For The HSCM can also be configured as ahigh-seed repeater for applications requiring distances beyond the specifidlimitations and network wiring information for the HS-NCM refer to the High-Speed NotiFire*Ner Marual.

For instructions on the additional capabilities available with the DVC-EM refer to the DVC ancd DAA Series Installation Marual.

Input power requirements: 24 VDC 0.400 A regulated power-limited patible power supply UL/ULC listed forfire proteetive signalling use.Communications circuit requirements: Refer to the High-Speed NotiFire*Net Manual for segment length limitations.

Communication Circuit Voltage and Current Rating/ProtocolTB4 (Ch A - Wire Only) 10 VDC 25mATB5 (Ch B - Wire Only) 10 VDC 25mAJ6 (NUP) 232 Protocol(N) 232 ProtocolJ13 (USBA) Standard ProtocolJ14 (USBB) Standard Protocol

Table 1 Voltage and Current Ratings for Communication Circuits

NOTE:FwiththeNFS40F64F320 FS3030F3030 DVC-EMCAadNCA the HS-NCM must be connected via the NUP Ports!

2TheNetworkCommunicationsModuleforWire(Hs-ncm-w)

Supports twisted-pair wire medium.(Class A) operation. NFPA Style 4 (Class B) operation or NFPA Style 7Transformer coupling provides eleetrical isolationbetween nodes.Pluggable terminal wiring with strain relief. Pluggable service connector (feeds signal directlya node (HS-NBB). through) in the event that power must be removed fromData is regenerated at each node.Two network ports to allow simultaneous connection of up to two fire alarm control panels and a programming puter.Enables software and database upload/download overHigh-Speed NotiFire*Net.

3TheNetworkCommunicationsModuleforFiber(Hs-ncM-MF Hs-NCM-sF HS-NCM-MFSF)

NFPA Style 4 (Class B) or Style 7 (Class A) operation. Supports fiber-optic medium.Data is immune to all environmental noise.Optical isolation prevents ground loops.Fiber type: High-Speed NotiFire*Net fiber-optic medium.▪ 62.5/125 micrometers (multi-mode 10 dB limit)• 50/125 micrometers (multi-mode 6.5 dB limit)• 9/125 micrometers (single-mode 30 dB limit) Wavelength (1): 1310 nanometers.Fiber Connectors: LC style.Two network ports to allow simultaneous connection of up Data is regenerated at each node.to two fire alarm control panels and a programmingputer. Enables software and database upload/download overHigh-Speed NotiFire*Net.

Figure 2 HS-NCM-SF/MF/MFSF

NOTE: When referring to fiber-optic cables the term MF* indicates a mult-mode fiber and the term °SF* indicates a single-mode fiber.

4TheNetworkCommunicationsModuleforWire/Fiber(Hs-ncM-wMF HS-NCM-WSF)

Supports twisted-pair wire and fiber-optic medium.NFPA Style 4 (Class B) or Style 7 (Class A) operation.network. Allows wire and fiber-optic nodes to municate as oneFiber type:▪ 62.5/125 micrometers (multi-mode 10 dB limit)▪50/125 micrometers (multi-mode 6.5 dB limit) • 9/125 micrometers (single-mode 30 dB limit)Wavelength (1): 1310 nanometers.Wire Connectors: Pluggable termminal wiring with strain Fiber Connectors: LC style.relief.Data is regenerated at each node.Two network ports to allow simultaneous connection of up to two fire alarm control panels and a programmingputer.Enables software and database upload/download over High-Speed NotiFire*Net. Port A and Port B assignment for the wire and fiber connections are set through VeriFire Tools. Refer to theVeriFireTM Tools CD on-line help file.

Figure3 HS-NCM-WSF/WMF

5HS-NCMConfiguration

HS-NCM configuration changes are made via the VeriFire Tools Programming Utility version 5.7 or higher.

VeriFire Tools can be connected to the HS-NCM via two different methods:

▪VeriFire Tools connected to any node on a network using the HS-NCM for network munication. •HS-NCM directly connected to VeriFire Tools.

via the NUP connection at the fire panel external power is needed. Refer to “External Power forHS-NCM Applications* on page 12

Perform the following steps to modify the HS-NCM’s configuration parameters using VeriFire Tools. Refer to theVeriFire Tools CD on-line help file.

Connect VeriFire Tools to the network or directly connected to the HS-NCM. source.3. In VeriFire Tools access the Upload/Download Screen:

Connect the HS-NCM to the FACP via either NUP port or provide power from an external UL/ULC listed power

In the “Network Node Session" of the Upload/Download screen find the node connected to the HS-NCM beingconfigured.

NOTE: When the HS-NCM is directly connected to the VeriFire Tols the node listed in the e se umous s ueos peooedn so ue eu ouoss p ome.VeriFire”

6.Using the mouse right click on the node connected to the HS-NCM being configured. A menu of available options is displayed.

5.Double lick the node to log in to the panel.

资源链接请先登录(扫码可直接登录、免注册)
①本文档内容版权归属内容提供方。如果您对本资料有版权申诉,请及时联系我方进行处理(联系方式详见页脚)。
②由于网络或浏览器兼容性等问题导致下载失败,请加客服微信处理(详见下载弹窗提示),感谢理解。
③本资料由其他用户上传,本站不保证质量、数量等令人满意,若存在资料虚假不完整,请及时联系客服投诉处理。
④本站仅收取资料上传人设置的下载费中的一部分分成,用以平摊存储及运营成本。本站仅为用户提供资料分享平台,且会员之间资料免费共享(平台无费用分成),不提供其他经营性业务。
投稿会员:匿名用户
我的头像

您必须才能评论!

手机扫码、免注册、直接登录

 注意:QQ登录支持手机端浏览器一键登录及扫码登录
微信仅支持手机扫码一键登录

账号密码登录(仅适用于原老用户)