CleanAgentExtinguishingSystemUnits GAQF.EX15566
Page Bottom
CleanAgentExtinguishingSystemUnits
See General Information for_Clean Agent Extinguishing System Units
FIRE EATER
EX15566
3400 HILLEROD DENMARK
or80 liters of IG-541 (Inergen) respectively. The units are pressurized to 200 (2900 psig) or 300 bar (4350 psig) with operating temperatures of ENGIINEERED UNIT IG-541 (Inergen) Clean Agent Extinguishing System Units stored pressure type having nominal charging capacities of 5032°F (0°C) to 150°F (65°C). The units are designed for total-flooding protection against Class A surface burning Class B flammable liquid and Class C fires ocurring within an enclosure.
A description of these extinguishing system units and the design and instalationmitations are contained in the Listee's installation manual Ci ULManual dted October 21 2011.These installations require the use of the Listee's flow calculation software IMT V2.0.37. Copies are available from the above Listee.
AGENT STORAGE CONTAINERASSEMBLY
Weight of Agent (Ibs) Part No.Cylinder and valve assembly 50 Liter 200 bar- 32.8 Ibs Cylinder and valve assembly 80 Liter 200 bar- 53.4 Ibs 200610-60 200616-60Cylinder and valve assembly 50 Liter 300 bar- 45.5 Ibs 200615-60Cylinder and valve assembly 80 Liter 300 bar- 72.8 Ibs 200624-60
Copyright 2011 Underwriters Laboratories Inc @
underULsFollowUServiceOnlytheproductsearing theUMark should econidered tobe Listed andovered underULsFollow The appearance of a pany's name or product in this database does not in itself assure that products so identified have been manufacturedService. Always look for the Mark on the product.
UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide Information Designs and/or Listings (files) must be presented in their entirety and in a non-misleading manner without any manipulation of thedata (or drawings). 2. The statement Reprinted from the Online Certifications Directory with permission from Undenwriters Laboratories Inc. must appear adjacent to the extracted material. In addition the reprinted mafterial must include 8 copyright notice in the follwing format:*Copyright @ 2011 Underwriters Laboratories Inc.@*