CleanAgentFireExtinguishingSystems

These systems contain electrically nonconducting volatile or gaseous fire extinguishing agents that don't leave a residue uponevaporation(perNFPA2001paragraph1-3.1)Theyareeffective fortotalflodingprotectionagainst hazardsinvolvingliqud flammablematerialselectricalequpmentandrdinarysolldbustiblesinocupancyarrangementswhichproduceonlysufaceburning. In general these agents are not effective or appropriate for hazards which produce deep-seated buming or for those which involve chemicals containing their own oxygen (such as cellulose nitrate) metal hydrides or reactive metals (such as sodum magnesium or uranium).

CleanAgent systemsare simlarinmanyrespectstoHalon1301andcarbondioxide systemsDischargeof theagentbytotalfldingor local application may create atmospheric hazards to personnel.Toxic thermal deposition products can be minimized by fast fire detectioncoupled withrapidagent dischargePersonnel shouldnot remain n theareafollowing systemdischargeTableA5.1.1fNFPA 2001providesinformationon toxicologicalandphysiologicaleffectscoveredin thisequipment classificationTheNoObserved Adverse EffectLevel(NOAEL)isthehighestconcentrationatwhichnoadversephysiologicalortoxicologicaleffecthasbeenobserved. The Lowest Observed Adverse Effect Level LOAEL) is the lowest concentration at which an adverse physiological or toxicological effect has been observed.

specificallyreference the relevant agent Approval. Individual agent litings appear under the category Clean Extinguishing Agents. Systems can only be FM Approved under this classificationif they use agents having a ponent Approval.The system Approvals

Compatible FM Approvals controls must be used. (See AUTOMATIC RELEASES FOR EXTINGUISHING SYSTEMS AND OTHER FIRE PROTECTION EQUIPMENT under ELECTRICAL SIGNALING.)

installationRequireddesign concentrations aryfrom agenttoagentand dependinguponmaximumdesignparametersthe concentrationmayvaryamong systemmanufacturers.hedesignconcentrations listedby thesystemmanufacturersaregenerallyaccepted in electrical/electronic hazards l.e. puter telemunication areas provided that Class A ordinary bustibles are kept to a minimum thereby minimizing the potential for a deep seated Class A fire.

uesda pnouddy W e no janoenuew eu Aq Auo uop eq leus bujfueuou pue Sufieuo wetss

Extinguishing Systems1994 Editionand must be listed in the United States Environmental Protection Agency (EPA) Significant ew Alternatives Policy (SNAP) as an acceptable substitute to Halon 1301.

Jurisdictions outside the United Statesmay notrecognize NFPA and EPA sanction of certain clean agents. Local and national

*Alternative to Halon 1211 and Halon 1301.

Control Inert Inergen CleanAgentFire Extinguishing Systems

System Designation: Control Inert Inergen Clean Agent Fire Extingulishing SystemsSystem Type: EngineeredAgent Identification: Inergen (Identified as IG-541 in NFPA 2001)Available Agent Storage Pressures: 200 bar 300 barMinimum and Maximum Agent 60°F to 80°F (15°C to 27°C) for multiple hazard unbalanced systemsStorage Temperatures: 32°F to 150°F (0°C to 65°C) for single hazard unbalanced systemsAvailable Nozzle Types: 360°Maximum Nozzle Area of Coverage: 24 ft by 24 ft (7.3 m by 7.3 m) 17 ft (5.2 m) maximum distance to farthest cornerMinimum and Maximum Nozzle Installation Height per Row: 0.3 ft to 15.4 ft (0.1 m to 4.7 m)Minimum and Maximum Height of 1.0 ft to 15.4 ft (0.3 m to 4.7 m)Protected Area per Nozzle Row:Hazard Class: Minimum Design Concentration for Class A 37.45% Class B 41.55%Design Itallonration Fire Eater Control Inert Ci Manual forUL Listed FM Approved Extinguishing System.Maintenance Manual: P/N Ci Manual 2014 FM-UL Rev. 2014-10-26Flow Calculation Software: Fire Eater Inergen Management Tool (IMT) flow calculation program Version 2.2.0 utilizing Flow Sim Engine dated 2014-08-27

Approval Guide

Limitations or Exceptions to the Limitations as defined in the manual and software and listed aboveApproval:Approved Filling Faities: Turanka 94 Air Products62700 Brmo Czech Republic

Company Name: Fire Eater A/SCompany Address: Valundsvej 17 3400 Hillerad DenmarkNew/Updated Product Listing: Company Website: NoListing Country: DenmarkAgent Type: INERGEN Engineered SystemCertification Type: FM Approved

资源链接请先登录(扫码可直接登录、免注册)
①本文档内容版权归属内容提供方。如果您对本资料有版权申诉,请及时联系我方进行处理(联系方式详见页脚)。
②由于网络或浏览器兼容性等问题导致下载失败,请加客服微信处理(详见下载弹窗提示),感谢理解。
③本资料由其他用户上传,本站不保证质量、数量等令人满意,若存在资料虚假不完整,请及时联系客服投诉处理。
④本站仅收取资料上传人设置的下载费中的一部分分成,用以平摊存储及运营成本。本站仅为用户提供资料分享平台,且会员之间资料免费共享(平台无费用分成),不提供其他经营性业务。
投稿会员:匿名用户
我的头像

您必须才能评论!

手机扫码、免注册、直接登录

 注意:QQ登录支持手机端浏览器一键登录及扫码登录
微信仅支持手机扫码一键登录

账号密码登录(仅适用于原老用户)