施工技术2014年1月上 64CONSTRUCTIONTECHNOLOCY第43卷第1期 DO1;10. 7672/ sgjs2014010064
深基坑软土地基地源热泵直埋式换热管施工技术
童仙敏 (浙江环宇建设集团有限公司,浙江绍兴312000)
[摘要]绍兴市文化中心地源热泵直埋式换热管因节地要求,需在流塑状淤泥质软土地基中施工,施工难度较大。
通过创新工艺施工,先浇筑操作垫层,再钻孔埋管,有效解决了软土地基钻机施工承载力不足、泥浆不能及时外运 与施工交叉污染的难题。
[关键词】地基:软土;地源热泵;直埋式换热管;施工技术 [中图分类号】TU753[文献标识码】A[文章编号】1002-8498(2014)01-0064-03
Source Heat Pump in Soft Soil Foundation Tong Xianmin (Zhejiang Huanyu Construction Group Co.,Lid.,Shaoxing,Zhejiang 312000, China) Abstract:Because of the limited space in Shaoxing City Culture Center,direct-buried heat-exchange pipe has to be constructed in soft soil foundations. Because of the great difficulty in the construction,a new method that construct the operation cushion first, and then to bury the pipes was adopted. This method has effectively solved the problem of lack of carrying capacity in the soft foundation and prevented cross contamination. Key words: foundations; sof soil; ground source heat pump; direct-buried heat-exchange pipes; construction 1直埋式换热管地源热泵系统原理~5层为办公及培训教室。
其中地下室占地面积 地源热泵是利用地能或地表浅层地热温度一9664㎡²,地源热泵有地埋管和机房安装2个部分, 年四季相对稳定的特性,冬季把地下土壤的热量转地埋管系统共设1340口45~50m深井,建筑物外 移到建筑物内,夏季则把地下冷量转移到建筑物侧布置804口井。
因场地限制,地下室底板下需布 内,通过完成与地热的交换达到制冷或制热效果,置孔深45m、间距约4m的地埋竖管井共536口,钻 是一种既节能又环保的绿色能源利用方式。
孔直径110mm,垂直埋管为U形PE管(Dn25),水 直埋式换热管地源热泵系统是在钻孔间置入U平管(PE管,Dn25~Dn63)在地下室底板下埋深约 的PE管连接,与地源热泵形成一个密闭的循环管管后对地基承载特性并未有任何影响。
由于地下 路,与热泵和室内散热(风机盘管)循环体系组成地室底板根据人防及防水要求不能开孔,平面布置如 源热泵系统。
图1所示。
2工程概况根据地质勘察报告,有关土层自上而下为:①, :绍兴市文化中心总建筑面积55256m²,为地上杂填土埋深0.00~0.60m;①2粉质黏土埋深 5层、地下1层的框架结构,基础形式为桩-筏基础,0.60~2.50m;②淤泥质粉质黏土、夹黏质粉土理 筏板厚500mm,基础埋深6m(局部7m)。
地面以上深2.50~4.70m;③淤泥质黏土埋深4.70~ 各层使用功能为:1~2层为阅览室,3层为藏书库,416.90m;④粉质黏土埋深16.90~23.70m;③粉 质黏土埋深23.70~33.10m;粉质黏土埋深 [作者简介]童仙敏,高级工程师,国家一级注册建造师,E-mail:33.10~36.40m;2黏质粉土埋深36.40~ TXM958@ 126.40.10m;9含碎石粉质黏土埋深40.10~ [收稿日期】2013-02-15
万方数据
2014 No.1童仙敏:深基坑软土地基地源热泵直埋式换热管施工技术65 4.0004.000下100cm,钻孔,埋管,完成后铺100cm黄砂作为缓 竖直理管水平冲保护层,缺陷是流塑状淤泥质土承载力极差,钻 埋管机无法作业。
2)方案2土方先开挖至底板垫层底面以下 100cm,再回填黄砂至垫层底,钻机在砂垫层上钻 孔,其缺点如下:①因淤泥质土承载力极低,汽车不 能行驶,约...